Note<br />
Note<br />
1. For a 400-V Inverter, if the carrier frequency is set to a value higher than the default<br />
setting, the Inverter overload “OL2” detection value will decrease in consideration of<br />
an increase in the heat that will be generated by the change in the carrier frequency.<br />
2. Default settings vary with the Inverter model.<br />
Function No. Name Description Setting<br />
range<br />
Frequency n058 Jump frequency<br />
Set center value of jumping frequency in 0.0 to<br />
jump<br />
1 1-Hz 1Hz units.<br />
400.0<br />
n059 Jump frequency<br />
2 value is set to 0.0.<br />
Frequency jump function will be invalid if<br />
n060 Jump frequency<br />
Set jump range of jumping frequency in 0.0 to<br />
1-Hz units.<br />
25.5<br />
range<br />
Accumulated<br />
operation<br />
time<br />
n061<br />
n062<br />
n063<br />
Total operating<br />
time<br />
function<br />
selection<br />
Total operating<br />
time 1<br />
(rightmost<br />
4 digits)<br />
Total operating<br />
time 2<br />
(leftmost 2<br />
digits)<br />
DC braking n064 DC braking<br />
current<br />
Torque<br />
compensation<br />
n065<br />
n066<br />
n067<br />
n068<br />
n069<br />
Stopped<br />
DC braking<br />
time<br />
Startup DC<br />
braking<br />
time<br />
Automatic<br />
torque<br />
boost gain<br />
Motor winding<br />
resistance<br />
Motor iron<br />
loss<br />
0: Accumulates power-on time.<br />
1: Accumulates running time<br />
Set accumulation start time in 1-h units.<br />
Permits accumulated operation time monitor<br />
to function. (Same as U-11 and U-12)<br />
Accumulated operation time (h) = n063 x<br />
10,000000 + n062<br />
Max. value: 279,620 (h) (Returns to 0<br />
when accumulated operation time exceeds<br />
279,620 h)<br />
Set DC control current in 1% units based<br />
on rated output current of Inverter as<br />
100%.<br />
Set stop DC control time and start DC<br />
control time in 1-s units.<br />
0, 1 1<br />
0 to<br />
9,999<br />
Default<br />
setting<br />
0.0<br />
0.0<br />
1.0<br />
0<br />
0 to 27 0<br />
0 to<br />
100<br />
0.0 to<br />
10.0<br />
DC control will be invalid if value is set to<br />
0.0. 0.0 to<br />
10.0<br />
Set automatic torque boost gain.<br />
Setting is usually not necessary.<br />
Set motor constant for automatic torque<br />
boost operation.<br />
Setting is usually not necessary.<br />
0.0 to<br />
3.0<br />
0.000<br />
to<br />
65.53<br />
0 to<br />
9,999<br />
50<br />
0.5<br />
0.0<br />
1.0<br />
See<br />
note<br />
See<br />
note