Note<br />

Note<br />

Note<br />

Note<br />

Note<br />

1. The Inverter in speed search operation will work according to the speed search V/f<br />

characteristics set with n054 and when the output current becomes less than the<br />

speed search operation level set with n052, the Inverter will have normal acceleration<br />

output.<br />

2. The speed search command must be ON for at least the minimum baseblock time set<br />

with n053 after the run command is input, otherwise the speed search operation is not<br />

available.<br />

3. Adjust the minimum baseblock time set with n053 for the most suitable timing to start<br />

the speed search operation.<br />

4. It is usually not necessary to change the default-set values of n052 and n054. Set<br />

n052 to a smaller value if the motor does not restart after the speed search operation<br />

completes.<br />

5. Input the run command in 5 ms or more after the speed search command is input to<br />

permit the Inverter to be in reliable speed search operation.<br />

Integral Value of PID Control Reset Command/PID Control Invalidating<br />

Command (Set Value = 18 or 19)<br />

• Integral Value Reset (Set Value = 18)<br />

If the integral value reset command is input, the integral value used for<br />

PID control will be reset and the integral operation output will be zero.<br />

The integral operation output will remain zero while this command is<br />

input.<br />

Input this command to stop the integral operation to temporarily prevent<br />

rapid changes of the output of the Inverter.<br />

• PID Control Invalidating Command (Set Value = 19)<br />

Use this command to change the type of control performed by the Inverter<br />

from PID control, such as JOG control, to the usual control,<br />

such as constant speed control with a frequency reference, and vice<br />

versa.<br />

The Inverter will stop performing PID control if this command is input<br />

and the Inverter will use input to the FV terminal as a frequency reference.<br />

If n002 is set to 0 or 1, however, the Inverter will use frequency<br />

references 1 to 4.<br />

Timer Function Input (Set Value = 20)<br />

Timer function input is a standard sequential input. By setting appropriate<br />

delay time values with n077 and n078, the Inverter can prevent the<br />

sensor from chattering.<br />

The Inverter will turn ON timer function output if timer function input to<br />

the Inverter is ON for a period longer than the timer function ON-delay<br />

time set with n077.<br />

The Inverter will turn OFF timer function output if timer function input to<br />

the Inverter is OFF for a period longer than the timer function OFF-delay<br />

time set with n078.<br />

Operation Example<br />