1. The Inverter in speed search operation will work according to the speed search V/f<br />
characteristics set with n054 and when the output current becomes less than the<br />
speed search operation level set with n052, the Inverter will have normal acceleration<br />
output.<br />
2. The speed search command must be ON for at least the minimum baseblock time set<br />
with n053 after the run command is input, otherwise the speed search operation is not<br />
available.<br />
3. Adjust the minimum baseblock time set with n053 for the most suitable timing to start<br />
the speed search operation.<br />
4. It is usually not necessary to change the default-set values of n052 and n054. Set<br />
n052 to a smaller value if the motor does not restart after the speed search operation<br />
completes.<br />
5. Input the run command in 5 ms or more after the speed search command is input to<br />
permit the Inverter to be in reliable speed search operation.<br />
Integral Value of PID Control Reset Command/PID Control Invalidating<br />
Command (Set Value = 18 or 19)<br />
• Integral Value Reset (Set Value = 18)<br />
If the integral value reset command is input, the integral value used for<br />
PID control will be reset and the integral operation output will be zero.<br />
The integral operation output will remain zero while this command is<br />
input.<br />
Input this command to stop the integral operation to temporarily prevent<br />
rapid changes of the output of the Inverter.<br />
• PID Control Invalidating Command (Set Value = 19)<br />
Use this command to change the type of control performed by the Inverter<br />
from PID control, such as JOG control, to the usual control,<br />
such as constant speed control with a frequency reference, and vice<br />
versa.<br />
The Inverter will stop performing PID control if this command is input<br />
and the Inverter will use input to the FV terminal as a frequency reference.<br />
If n002 is set to 0 or 1, however, the Inverter will use frequency<br />
references 1 to 4.<br />
Timer Function Input (Set Value = 20)<br />
Timer function input is a standard sequential input. By setting appropriate<br />
delay time values with n077 and n078, the Inverter can prevent the<br />
sensor from chattering.<br />
The Inverter will turn ON timer function output if timer function input to<br />
the Inverter is ON for a period longer than the timer function ON-delay<br />
time set with n077.<br />
The Inverter will turn OFF timer function output if timer function input to<br />
the Inverter is OFF for a period longer than the timer function OFF-delay<br />
time set with n078.<br />
Operation Example<br />
Timer function<br />
input<br />
Timer function<br />
output