Function No. Name Description Setting<br />

range<br />

Overtorque n074<br />

0 to 4 0<br />

detection<br />

Timer function<br />

Braking Resistor<br />

Unit<br />

overheating<br />

protection<br />

I/O phase<br />

loss detection<br />

n075<br />

n076<br />

n077<br />

n078<br />

n079<br />

n080<br />

n081<br />

n082<br />

Overtorque<br />

detection<br />

function<br />

selection<br />

Overtorque<br />

detection<br />

level<br />

Overtorque<br />

detection<br />

time<br />

Timer function<br />

ON<br />

delay time<br />

Timer function<br />

OFF<br />

delay time<br />

Braking resistor<br />

overheating<br />

protection<br />

selection<br />

Input openphase<br />

detection<br />

level<br />

Input openphase<br />

detection<br />

time<br />

Output<br />

open-phase<br />

detection<br />

level<br />

0: Inhibits Inverter from detecting overtorque.<br />

1: Inverter will detect overtorque only during<br />

speed agreement and continue running<br />

with warning after detection.<br />

2: Running Inverter will detect overtorque<br />

and continue running with warning after<br />

detection.<br />

3: Inverter will detect overtorque only during<br />

speed agreement and turn OFF<br />

output for safety when overtorque is<br />

detected.<br />

4: Running Inverter will always detect<br />

overtorque and turn OFF output for<br />

safety when overtorque is detected.<br />

Set overtorque detection current in 1%<br />

units based on rated output current of Inverter<br />

as 100%.<br />

Set overtorque detection time in 1-s units.<br />

Overtorque will be detected if current larger<br />

than value set with n075 flows for the<br />

set time or more.<br />

Set time lag between moment timer function<br />

input turns ON and moment timer<br />

function output turns ON.<br />

Valid if multi-function input and multi-function<br />

contact output are set to timer function.<br />

Set time lag between the moment the timer<br />

function input turns OFF and the<br />

moment the timer function output turns<br />

OFF.<br />

Valid if multi-function input and multi-function<br />

contact output are set to timer function.<br />

0: Inhibits overheating protection from<br />

functioning.<br />

1: Permits overheating protection to function.<br />

Set input phase loss detection level to percentage<br />

of main circuit DC voltage.<br />

200-V class: 200 VDC as 100%<br />

400-V class: 800 VDC as 100%<br />

Set input phase loss detection time.<br />

Detection time = 1.28 x n n081<br />

Inverter will detect input phase loss if voltage<br />

as large as or larger than value set<br />

with n080 is imposed continuously for period<br />

exceeding set time.<br />

Set output phase loss detection level in<br />

1% units based on rated output current of<br />

Inverter as 100%.<br />

Output phase loss detection will be invalid<br />

if value is set to 0.<br />

30 to<br />

200<br />

0.1 to<br />

10.0<br />

0.0 to<br />

25.5<br />

0.0 to<br />

25.5<br />

0, 1 0<br />

1 to<br />

100<br />

2 to<br />

255<br />

0 to<br />

100<br />

Default<br />

setting<br />

160<br />

0.1<br />

0.0<br />

0.0<br />

7<br />

8<br />

0