OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Set Values<br />
Set<br />
Description<br />
value<br />
0 Deceleration stop in deceleration time 1 set with n020<br />
1 Free running stop<br />
2 Deceleration stop in deceleration time 2 set with n022<br />
3 Continuous operation with warning<br />
Note If n034 is set to 3, the Inverter will display “OH1” when the temperature of the heat sink<br />
reaches approximately 90°C and the Inverter will continue running. If “OH1” is displayed,<br />
use a cooling fan or air conditioner to cool the Inverter. The Inverter will detect the heat<br />
sink overheat warning OH2 if the temperature further rises after “OH1” is displayed. The<br />
Inverter will stop running immediately after OH2 is detected to protect its power module<br />
from damage so that the motor will coast to stop.<br />
n035<br />
Multi-function Input 1 (S2)<br />
Setting range 0 to 24 Unit --- Default setting<br />
n036<br />
Multi-function Input 2 (S3)<br />
Setting range 2 to 24 Unit --- Default setting<br />
n037<br />
Multi-function Input 3 (S4)<br />
Setting range 2 to 24 Unit --- Default setting<br />
n038<br />
Multi-function Input 4 (S5)<br />
Setting range 2 to 24 Unit --- Default setting<br />
n039<br />
Multi-function Input 5 (S6)<br />
Setting range 2 to 25 Unit --- Default setting<br />
0<br />
2<br />
4<br />
9<br />
10<br />
• The parameters n035 to n039 can be set to the following.<br />
• Each of the set values of n035 to n039 must be unique.