n<br />

Carrier 0frequency (fc)<br />

5<br />

2.5 kHz<br />

0<br />

=<br />

7<br />

1.0 kHz<br />

n<br />

Carrier 0frequency (fc)<br />

5<br />

2.5 kHz0<br />

=<br />

8<br />

1.0 kHz<br />

n<br />

Carrier 0frequency (fc)<br />

5<br />

2.5 kHz<br />

0<br />

=<br />

9<br />

1.0 kHz<br />

Output frequency<br />

83.3 Hz 208.3 Hz<br />

(fout)<br />

41.6 Hz 104.1 Hz<br />

Output frequency<br />

(fout)<br />

27.7 Hz 69.4 Hz<br />

Output frequency<br />

(fout)<br />

n051<br />

Selection of Running After Restoration Following a<br />

Momentary Stop<br />

Setting range 0, 1, and 2 Unit --- Default setting<br />

0<br />

• Select with n051 a method to process instantaneous power failure.<br />

Set Values<br />

Set<br />

Description<br />

value<br />

0 Inverter will discontinue running.<br />

1 Inverter will continue running if power is supplied again within instantaneous power<br />

failure compensation time set with n055. (see note 1)<br />

2 Inverter will always continue running without detecting UV1 or UV3. (see notes 1 and 2)<br />

Note 1. Keep the run command ON to permit the Inverter to restart operation automatically<br />

when power is supplied to the Inverter after the operation of the Inverter is interrupted<br />

due to an instantaneous power failure.<br />

Note 2. If n051 is set to 2, the Inverter will restart running after supply voltage to the Inverter<br />

returns to normal and the Inverter will not detect error output signals.<br />

n052<br />

Speed Search Control Level<br />

Setting range 0 to 200 Unit % (Rated output<br />

current ratio)<br />

Default setting<br />

150<br />

• Set with n052 a current level in 1% units based on the rated output current<br />

as 100% which enables the Inverter to determine the completion<br />

of the speed search control.<br />

• It is usually not necessary to change the default-set value.<br />

• To permit the Inverter to use the speed search function, set the multifunction<br />

input parameter used by the Inverter to 15 or 16 so that the<br />

speed search command will be input to the Inverter.<br />

• When the output current becomes less than the value set with n054,<br />

the Inverter in speed search control will detect the synchronous speed<br />

and the Inverter will be in acceleration mode.