n012<br />
Maximum Frequency (FMAX)<br />
Setting range 50.0 to 400.0 Unit Hz Default setting<br />
n013<br />
Setting range 0.1 to 255.0<br />
(510.0)<br />
n014<br />
Maximum Voltage (VMAX)<br />
Unit V Default setting<br />
Maximum Voltage Frequency (FA)<br />
Setting range 0.2 to 400.0 Unit Hz Default setting<br />
n015<br />
Intermediate Output Frequency (FB)<br />
Setting range 0.1 to 399.9 Unit Hz Default setting<br />
n016<br />
Setting range 0.1 to 255.0<br />
(510.0)<br />
n017<br />
Intermediate Output Frequency Voltage (VC)<br />
Unit V Default setting<br />
Minimum Output Frequency (FMIN)<br />
Setting range 0.1 to 10.0 Unit Hz Default setting<br />
n018<br />
Setting range 0.1 to 50.0<br />
(100.0)<br />
Minimum Output Frequency Voltage (VMIN)<br />
Unit V Default setting<br />
Note Figures in parentheses apply to the 400-V Inverter.<br />
Optional V/f Pattern in Detail<br />
Voltage<br />
60.0<br />
200.0 (400.0)<br />
60.0<br />
3.0<br />
15.0 (30.0)<br />
1.5<br />
10.0 (20.0)<br />
Frequency<br />
(Hz)<br />
Note The V/f pattern is a straight line if there is no difference between n015 and n017 in set<br />
value, in which case the set value of n016 will be ignored.<br />
Interruption Mode and Protective Function Selection (n003, n004,<br />
n008, n032, and n033)<br />
Set the input voltage of the Inverter to determine the voltage protective level of the Inverter.