n012<br />

Maximum Frequency (FMAX)<br />

Setting range 50.0 to 400.0 Unit Hz Default setting<br />

n013<br />

Setting range 0.1 to 255.0<br />

(510.0)<br />

n014<br />

Maximum Voltage (VMAX)<br />

Unit V Default setting<br />

Maximum Voltage Frequency (FA)<br />

Setting range 0.2 to 400.0 Unit Hz Default setting<br />

n015<br />

Intermediate Output Frequency (FB)<br />

Setting range 0.1 to 399.9 Unit Hz Default setting<br />

n016<br />

Setting range 0.1 to 255.0<br />

(510.0)<br />

n017<br />

Intermediate Output Frequency Voltage (VC)<br />

Unit V Default setting<br />

Minimum Output Frequency (FMIN)<br />

Setting range 0.1 to 10.0 Unit Hz Default setting<br />

n018<br />

Setting range 0.1 to 50.0<br />

(100.0)<br />

Minimum Output Frequency Voltage (VMIN)<br />

Unit V Default setting<br />

Note Figures in parentheses apply to the 400-V Inverter.<br />

Optional V/f Pattern in Detail<br />

Voltage<br />

60.0<br />

200.0 (400.0)<br />

60.0<br />

3.0<br />

15.0 (30.0)<br />

1.5<br />

10.0 (20.0)<br />

Frequency<br />

(Hz)<br />

Note The V/f pattern is a straight line if there is no difference between n015 and n017 in set<br />

value, in which case the set value of n016 will be ignored.<br />

Interruption Mode and Protective Function Selection (n003, n004,<br />

n008, n032, and n033)<br />

Set the input voltage of the Inverter to determine the voltage protective level of the Inverter.