OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Set Values<br />
Set value Run command Frequency reference<br />
0 Digital Operator Digital Operator<br />
1 Control circuit terminals Digital Operator<br />
2 Digital Operator Control circuit terminals<br />
3 Control circuit terminals Control circuit terminals<br />
Note Do not set n002 to any value other than the above.<br />
Frequency Reference Type Selection (n042, n046, and n047)<br />
through Control Circuit Terminal<br />
Select the FV terminal to input the frequency reference within a voltage range from 0 to 10<br />
VDC or the FI terminal to input the frequency reference within a current range from 4 to 20<br />
mA with n042.<br />
n042<br />
Analog Frequency Reference Voltage/Current Selection<br />
Setting range 0, 1 Unit --- Default setting<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 The FV terminal can be used for the analog frequency reference within a voltage range<br />
from 0 to 10 VDC.<br />
1 The FI terminal can be used for the analog frequency reference. Set the input level with<br />
n043.<br />
0<br />
Note<br />
Note<br />
1. The FI terminal is a current input terminal for 4 to 20 mA. The FI terminal can be a<br />
voltage input terminal by changing the FI input level with n043 and cutting jumper wire<br />
of the PCB. Do not, however, change the FI terminal to a voltage input terminal unless<br />
the Inverter is used for PID control.<br />
2. Set n042 according to the type of frequency reference.<br />
Set the frequency reference gain with n046 and the frequency reference bias with n047.<br />
n046<br />
Frequency Reference Gain<br />
Setting range 0 to 200 Unit % Default setting<br />
100<br />
n047<br />
Frequency Reference Bias<br />
Setting range –100 to 100 Unit % Default setting<br />
0<br />
Set Values<br />
n046: The frequency for 10-V or 20-mA input can be set in 1% units based on the maximum<br />
frequency set with n012 as 100%.