OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Energy-saving Control Settings<br />
n095<br />
Energy-saving Control Selection<br />
Setting range 0, 1 Unit --- Default setting<br />
0<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 Inhibits the Inverter from performing energy-saving control.<br />
1 Permits the Inverter to perform energy-saving control.<br />
Note Set n095 to 1 so that the Inverter will perform energy-saving control.<br />
n096<br />
Energy-saving Coefficient K2<br />
Setting range 0.00 to 655.0 Unit --- Default setting<br />
See note<br />
Note The default-set value of n096 varies with the Inverter model.<br />
Set Values<br />
Set the K2 value according to the capacity of the motor.<br />
The K2 value of each Inverter model is set to the following before shipping according to<br />
the maximum capacity of the motor that can be connected to the Inverter model.<br />
Capacity of motor<br />
(kW)<br />
200-V class 400-V class<br />
Energy-saving<br />
coefficient K2 (n096)<br />
Capacity of motor<br />
(kW)<br />
Energy-saving<br />
coefficient K2 (n096)<br />
0.4 288.2 0.4 576.4<br />
0.75 223.7 0.75 447.4<br />
1.5 169.4 1.5 338.8<br />
2.2 156.8 2.2 313.6<br />
3.7 122.9 3.7 245.8<br />
5.5 94.75 5.5 189.5<br />
7.5 72.69 7.5 145.4<br />
11 70.44 11 140.9<br />
15 63.13 15 126.3<br />
18 57.87 18 115.7<br />
22 51.79 22 103.6<br />
30 46.27 30 92.54<br />
37 38.16 37 76.32<br />
45 35.78 45 71.56<br />
55 31.35 55 67.20<br />
75 23.10 75 46.20<br />
--- --- 110 36.23<br />
160 30.13<br />
185 30.57<br />
220 27.13<br />
300 21.76<br />
Note<br />
1. The above K2 values are for standard motors and dedicated motors for inverters. The<br />
Inverter in energy-saving mode cannot save unnecessary power supply to high-