n029<br />
Setting range<br />
Inching Frequency Reference<br />
0 to maximum<br />
frequency<br />
Unit Set with n024 Default setting<br />
6.0<br />
• The inching frequency reference must be set with n029 if an inching<br />
frequency is required.<br />
• The inching command must be selected to use the inching frequency<br />
reference.<br />
n030<br />
Output Frequency Upper Limit<br />
Setting range 0 to 100 Unit % (Maximum<br />
frequency ratio)<br />
Default setting<br />
100<br />
n031<br />
Output Frequency Lower Limit<br />
Setting range 0 to 100 Unit % (Maximum<br />
frequency ratio)<br />
Default setting<br />
0<br />
• Set the upper limit and lower limit of the output frequency in 1% units<br />
based on the maximum frequency set with n012 as 100%.<br />
• The Inverter will operate at the lower limit of the output frequency set<br />
with n031 if the frequency reference used by the Inverter is set to 0.<br />
The Inverter will not, however, operate if n031 is set to a value smaller<br />
than the minimum output frequency set with n017.<br />
Internal frequency<br />
reference<br />
Output frequency<br />
upper limit (n030)<br />
Output frequency<br />
lower limit (n031)<br />
Set frequency reference<br />
n032<br />
Setting range 10% to 200%<br />
of rated output<br />
current of Inverter<br />
Motor Rated Current<br />
Unit A Default setting<br />
See note<br />
Note The default-set value varies with the Inverter model. Refer to the following table.<br />
Set Values<br />
• Set the rated input current of the motor to determine electronic thermal<br />
protection characteristics for the motor.<br />
• The parameter n032 is set to the rated input current of the maximum<br />
applicable motor before shipping.