Do not ground the secondary winding side of the transformer, otherwise the Inverter may<br />

break down.<br />

With Input Transformer for 12-pulse Rectification<br />

Input transformer for<br />

12-pulse rectification<br />

<strong>3G3HV</strong><br />

200 VAC (400 V)<br />

L1 (R)<br />

L2 (S)<br />

L3 (T)<br />

L11 (R1)<br />

L21 (S1)<br />

L31 (T1)<br />

T1 (U)<br />

T2 (V)<br />

T3 (W)<br />

With Standard Transformers for 12-pulse Rectification<br />

200 VAC (400 V)<br />

Star-star insulating<br />

transformer<br />

Star-delta insulating<br />

transformer<br />

<strong>3G3HV</strong><br />

L1 (R) T1 (U)<br />

L2 (S) T2 (V)<br />

L3 (T) T3 (W)<br />

L11 (R1)<br />

L21 (S1)<br />

L31 (T1)<br />

Note Use insulating transformers.<br />

• Input Transformers for 12-pulse Rectification<br />

Refer to the following table to select the input transformer for 12-pulse<br />

rectification. Refer to the minimum currents on the secondary winding<br />

side in the table when selecting two standard transformers used in<br />

combination for 12-pulse rectification.