When the Inverter is in normal operation for 10 minutes after an error retry.<br />

When the Inverter receives error reset input after the Inverter detects an error with a<br />

protection function.<br />

When the Inverter is turned OFF and ON.<br />

• To permit the Inverter to output an error retry signal, set the multi-function<br />

contact output parameter used by the Inverter to 12.<br />

n057<br />

Selection of Error Output during Error Retry<br />

Setting range 0, 1 Unit --- Default setting<br />

0<br />

Set Values<br />

• Select with n057 whether to permit the Inverter to turn ON error output<br />

while the Inverter is in error retry operation.<br />

• To permit the Inverter to turn ON error output while the Inverter is in<br />

error retry operation, set the multi-function contact output parameter<br />

used by the Inverter to 0.<br />

Set<br />

Description<br />

value<br />

0 Turns ON error output while error retry is performed.<br />

1 Turns OFF error output while error retry is performed.<br />

n058 Jump Frequency 1<br />

Setting range 0.0 to 400.0 Unit Hz Default setting<br />

0.0<br />

n059 Jump Frequency 2<br />

Setting range 0.0 to 400.0 Unit Hz Default setting<br />

0.0<br />

n060<br />

Jump Frequency Range<br />

Setting range 0.0 to 25.5 Unit Hz Default setting<br />

1.0<br />

• The frequency jump prevents the Inverter from generating frequencies<br />

that make the mechanical system resonate.<br />

• The frequency jump can be used effectively to make dead bands for<br />

frequency references.<br />

• Set with n058 and n059 the center values of jumping frequencies.<br />

• The value set with n059 must be as large as or larger than the value set<br />

with n059, otherwise OPE6 (improper parameter setting) will result.