OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Free Running Stop 1 with Timer (n004 = 2)<br />
Output frequency<br />
Deceleration rate determined by deceleration<br />
time 1 set with n020 or deceleration time 2<br />
set with n022.<br />
Run command<br />
ignored.<br />
Set the deceleration time<br />
to a period longer than<br />
the time required by the<br />
motor to coast to stop.<br />
Run command<br />
Note The run command will not be accepted during the minimum baseblock time set with n053<br />
if the time required by the motor to coast to stop is shorter than the minimum baseblock<br />
time.<br />
Free Running Stop 2 with Timer (n004 = 3)<br />
Output frequency<br />
Deceleration rate determined by deceleration<br />
time 1 set with n020 or deceleration time 2<br />
set with n022.<br />
Set the deceleration time<br />
to a period longer than<br />
the time required by the<br />
motor to coast to stop.<br />
Run command<br />
Note The run command will not be accepted during the minimum baseblock time set with n053<br />
if the time required by the motor to coast to stop is shorter than the minimum baseblock<br />
time.<br />
n005<br />
Forward/Reverse Rotation Selection<br />
Setting range 0, 1 Unit --- Default setting<br />
0<br />
• Set the rotation direction of the motor so that the motor will rotate in the<br />
set direction when the forward rotation command is input.<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 The motor seen from the load side rotates counterclockwise.<br />
1 The motor seen from the load side rotates clockwise.<br />
• The motor is deemed to be rotating forward if the motor seen from the<br />
load side is rotating counterclockwise unless the forward rotation<br />
direction of the motor defined by the manufacturer is opposite.<br />
n006<br />
Reverse Rotation-inhibit Selection<br />
Setting range 0, 1 Unit --- Default setting<br />
0<br />
• Select whether reverse rotation will be available or not.