Function<br />

No.<br />

Name<br />

Error retry n056 Number of<br />

error retries<br />

n057 Selection of<br />

error output<br />

during error<br />

retry<br />

Note<br />

Note<br />

Description<br />

Setting<br />

range<br />

Set number of error retries. 0 to 10<br />

[0]<br />

0: Turns ON error output while error retry 0, 1<br />

is performed.<br />

1: Turns OFF error output while error retry<br />

is performed.<br />

[0]<br />

User<br />

setting<br />

1. For a 400-V Inverter, if the carrier frequency is set to a value higher than the default<br />

setting, the Inverter overload “OL2” detection value will decrease in consideration of<br />

an increase in the heat that will be generated by the change in the carrier frequency.<br />

2. Default settings vary with the Inverter model.<br />

Function No. Name Description Setting<br />

range<br />

Frequency n058 Jump frequency<br />

Set center value of jumping frequency in 0.0 to<br />

jump<br />

1 1-Hz 1Hz units.<br />

400.0<br />

n059 Jump frequency<br />

2 value is set to 0.0.<br />

Frequency jump function will be invalid if<br />

[0.0]<br />

n060 Jump frequency<br />

Set jump range of jumping frequency in 0.0 to<br />

1-Hz units.<br />

25.5<br />

range<br />

[1.0]<br />

Accumulated<br />

operation<br />

time<br />

n061<br />

n062<br />

n063<br />

Total operating<br />

time<br />

function<br />

selection<br />

Total operating<br />

time 1<br />

(rightmost<br />

4 digits)<br />

Total operating<br />

time 2<br />

(leftmost 2<br />

digits)<br />

DC braking n064 DC braking<br />

current<br />

n065<br />

n066<br />

Stopped<br />

DC braking<br />

time<br />

Startup DC<br />

braking<br />

time<br />

0: Accumulates power-on time.<br />

1: Accumulates running time<br />

Set accumulation start time in 1-h units.<br />

Permits accumulated operation time monitor<br />

to function. (Same as U-11 and U-12)<br />

Accumulated operation time (h) = n063 x<br />

10,000000 + n062<br />

Max. value: 279,620 (h) (Returns to 0<br />

when accumulated operation time exceeds<br />

279,620 h)<br />

Set DC control current in 1% units based<br />

on rated output current of Inverter as<br />

100%.<br />

Set stop DC control time and start DC<br />

control time in 1-s units.<br />

DC control will be invalid if value is set to<br />

00 0.0.<br />

0, 1<br />

[1]<br />

0 to<br />

9,999<br />

[0]<br />

0 to 27<br />

[0]<br />

0 to<br />

100<br />

[50]<br />

0.0 to<br />

10.0<br />

[0.5]<br />

0.0 to<br />

10.0<br />

[0.0]<br />

User<br />

setting