Function No. Name Description Setting<br />

range<br />

Digital Operator<br />

n007 Operation 0: Inhibits Operation Mode Selection Key 0, 1<br />

func-<br />

direction from functioning.<br />

tion selection<br />

selection 1: Permits Operation Mode Selection Key<br />

key permit/ to function.<br />

inhibit<br />

[1]<br />

V/f pattern<br />

selection<br />

V/f pattern<br />

selection<br />

n008<br />

n009<br />

n010<br />

n011<br />

n012<br />

n013<br />

n014<br />

n015<br />

n016<br />

n017<br />

n018<br />

Stop Key<br />

function<br />

selection<br />

Frequency<br />

reference<br />

setting<br />

selection<br />

V/f pattern<br />

selection<br />

Rated input<br />

voltage of<br />

motor (see<br />

note)<br />

Maximum<br />

frequency<br />

(FMAX)<br />

Maximum<br />

voltage<br />

(VMAX)<br />

(see note)<br />

Maximum<br />

voltage frequency<br />

(FA)<br />

Intermediate<br />

output<br />

frequency<br />

(FB)<br />

Intermediate<br />

output<br />

frequency<br />

voltage<br />

(VC)<br />

(see note)<br />

Minimum<br />

output frequency<br />

(FMIN)<br />

Minimum<br />

output frequency<br />

voltage<br />

(VMIN)<br />

(see note)<br />

0: The STOP/RESET Key will function<br />

only when the Inverter is running with<br />

the run command through the Digital<br />

Operator.<br />

1: The STOP/RESET Key will function<br />

anytime.<br />

0: Permits frequency reference set with<br />

the Digital Operation to be valid without<br />

Enter Key input.<br />

1: Permits frequency reference set with<br />

the Digital Operation to be valid with<br />

Enter Key input.<br />

0to E: Selects from 15 fixed V/f patterns.<br />

F: Selects optional V/f pattern with n012<br />

to n018 settings.<br />

Set rated input voltage of motor with 1 V<br />

units.<br />

Voltage<br />

(V)<br />

Frequency<br />

(Hz)<br />

The V/f pattern will be a straight line if<br />

there is no difference between n015 and<br />

n017 in set value, in which case the set<br />

value of n016 will be ignored.<br />

0, 1<br />

[1]<br />

0, 1<br />

[1]<br />

0 to F<br />

[1]<br />

150.0<br />

to<br />

255.0<br />

[200.0]<br />

50.0 to<br />

400.0<br />

[60.0]<br />

0.1 to<br />

255.0<br />

[200.0]<br />

0.2 to<br />

400.0<br />

[60.0]<br />

0.1 to<br />

399.9<br />

[3.0]<br />

0.1 to<br />

255.0<br />

[15.0]<br />

0.1 to<br />

10.0<br />

[1.5]<br />

0.1 to<br />

50.0<br />

[10.0]<br />

User<br />

setting