Note<br />

2. To permit the Inverter to output a signal indicating that the Inverter is processing frequency<br />

reference loss, set n040 (i.e., multi-function contact output 1) or n041 (i.e.,<br />

multi-function contact output 2) to 14.<br />

n046<br />

Frequency Reference Gain<br />

Setting range 0 to 200 Unit % Default setting<br />

100<br />

n047<br />

Frequency Reference Bias<br />

Setting range –100 to 100 Unit % Default setting<br />

0<br />

• Set the frequency reference gain with n046 and the frequency reference<br />

bias with n047.<br />

Set Values<br />

• n046: The frequency for 10 V or 20 mA input can be set in 1% units based on<br />

the maximum frequency set with n012 as 100%.<br />

• n047: The frequency for 0 V or 4 mA input can be set in 1% units based on the<br />

maximum frequency set with n012 as 100%.<br />

Frequency reference<br />

Maximum frequency x<br />

frequency reference<br />

gain/100<br />

Maximum frequency x<br />

frequency reference<br />

bias/100<br />

0 V<br />

(4 mA)<br />

10 V<br />

(20 mA)<br />

Values in parentheses apply<br />

when the frequency reference<br />

is input with current.<br />

n048<br />

Multi-function Analog Output Selection<br />

Setting range 0, 1, 2, and 3 Unit --- Default setting<br />

0<br />

• Set the n048 so that the type of signal of multi-function analog output<br />

terminals AM and AC will be determined.<br />

Set Values (n048)<br />

Set<br />

Description<br />

value<br />

0 Output frequency (10 V: Max. frequency n012)<br />

1 Output current (10 V: Rated inverter current)<br />

2 Output power (10 V: Rated inverter output capacity)<br />

3 Main circuit DC voltage (10 V: 200-V class: 400 V; 400-V class: 800V)<br />

n049<br />

Multi-function Analog Output Gain<br />

Setting range 0.01 to 2.00 Unit Times Default setting<br />

1.00<br />

• The parameter n049 is used to adjust the analog output gain.<br />

Set Values<br />

• Set n049 to the result obtained from dividing the voltage of the full analog<br />

output by 10 V.