Note<br />
2. To permit the Inverter to output a signal indicating that the Inverter is processing frequency<br />
reference loss, set n040 (i.e., multi-function contact output 1) or n041 (i.e.,<br />
multi-function contact output 2) to 14.<br />
n046<br />
Frequency Reference Gain<br />
Setting range 0 to 200 Unit % Default setting<br />
100<br />
n047<br />
Frequency Reference Bias<br />
Setting range –100 to 100 Unit % Default setting<br />
0<br />
• Set the frequency reference gain with n046 and the frequency reference<br />
bias with n047.<br />
Set Values<br />
• n046: The frequency for 10 V or 20 mA input can be set in 1% units based on<br />
the maximum frequency set with n012 as 100%.<br />
• n047: The frequency for 0 V or 4 mA input can be set in 1% units based on the<br />
maximum frequency set with n012 as 100%.<br />
Frequency reference<br />
Maximum frequency x<br />
frequency reference<br />
gain/100<br />
Maximum frequency x<br />
frequency reference<br />
bias/100<br />
0 V<br />
(4 mA)<br />
10 V<br />
(20 mA)<br />
Values in parentheses apply<br />
when the frequency reference<br />
is input with current.<br />
n048<br />
Multi-function Analog Output Selection<br />
Setting range 0, 1, 2, and 3 Unit --- Default setting<br />
0<br />
• Set the n048 so that the type of signal of multi-function analog output<br />
terminals AM and AC will be determined.<br />
Set Values (n048)<br />
Set<br />
Description<br />
value<br />
0 Output frequency (10 V: Max. frequency n012)<br />
1 Output current (10 V: Rated inverter current)<br />
2 Output power (10 V: Rated inverter output capacity)<br />
3 Main circuit DC voltage (10 V: 200-V class: 400 V; 400-V class: 800V)<br />
n049<br />
Multi-function Analog Output Gain<br />
Setting range 0.01 to 2.00 Unit Times Default setting<br />
1.00<br />
• The parameter n049 is used to adjust the analog output gain.<br />
Set Values<br />
• Set n049 to the result obtained from dividing the voltage of the full analog<br />
output by 10 V.