Function No. Name Description Setting<br />
range<br />
Slip compensation<br />
Motor rated<br />
0.0 to<br />
slip<br />
9.9<br />
Others<br />
n109<br />
(see<br />
note 1)<br />
n110<br />
(see<br />
note 1)<br />
n111<br />
(see<br />
note 1)<br />
n112<br />
(see<br />
note 1)<br />
n113<br />
(see<br />
note 1)<br />
n114<br />
(see<br />
note 1)<br />
n115<br />
(see<br />
note 1)<br />
Motor noload<br />
current<br />
Slip compensation<br />
primary<br />
delay time<br />
Operation<br />
selection<br />
when Digital<br />
Operator<br />
is disconnected<br />
Frequency<br />
detection<br />
width<br />
Local/Remote<br />
Key<br />
selection<br />
When use slip compensation function, sets<br />
the motor rated slip in % units of motor<br />
rated frequency.<br />
Sets the motor no-load current in % unit of<br />
motor rated current (n032).<br />
Slip compensation primary delay time is<br />
set in s unit.<br />
Note Usually setting is not necessary. Adjust<br />
when slip compensation responsiveness<br />
is low, or speed is not stabilized.<br />
When responsiveness is low, decrease<br />
the set value.<br />
When speed is not stabilized, increase<br />
the set value.<br />
Sets the operation when the Digital Operator<br />
is disconnected.<br />
0: Disabled (operation continues even if<br />
the Digital Operator is disconnected.)<br />
1: Enabled (CPF0 or CPF1 is detected<br />
with Digital Operator. Inverter output<br />
will be cut off and error contact will be<br />
operated.)<br />
Sets the width of Frequency Agreement<br />
(n040, n041) and frequency detection<br />
(n073) in Hz unit.<br />
Used to set the Operation mode by switching<br />
to the Remote mode using the Local/<br />
Remote Key.<br />
0: Run signals that are input during mode<br />
switching are ignored. (Input Run signals<br />
after switching the mode.)<br />
1: Run signals become effective immediately<br />
after switching to the Remote<br />
mode.<br />
For the manufacturer’s use. (Not setting)<br />
[0.0]<br />
0 to 99<br />
0.0 to<br />
25.5<br />
[2.0]<br />
0, 1<br />
[0]<br />
0.0 to<br />
25.5<br />
[2.0]<br />
0, 1<br />
[0]<br />
See<br />
note 2<br />
User<br />
setting<br />
Note<br />
Note<br />
1. These constant are disabled for 1010 to 1015 of PROM number (U-10).<br />
2. Setting range and default settings vary with the Inverter model.