Set Values<br />

Set<br />

Description<br />

value<br />

0 Reverse rotation/Stop (2-wire sequence selection) (Only n035 can be set<br />

to 0)<br />

1 Stop command (3-wire sequence selection) (Only n035 can be set<br />

to 1)<br />

S1 will be used for the run command and S3 will be used for forward/reverse rotation<br />

instruction and the value set with n036 will be ignored.<br />

2 External error (NO contact: ON)<br />

3 External error (NC contact: ON)<br />

4 Error reset (ON: Valid) Error reset will be ignored if the Inverter is running normally.<br />

5 Operation mode selection (ON: Digital Operator; OFF: n002)<br />

6 Not used<br />

7 Emergency stop (ON: The Inverter will decelerate to stop the motor according to<br />

acceleration time 2 set with n022)<br />

To restart the Inverter, turn the run command OFF and ON.<br />

8 Analog input selection (ON: Current input through FI terminal; OFF: FV terminal)<br />

Current input through the FI terminal will be valid if the FI terminal is selected with n042<br />

(i.e., analog frequency reference voltage/current selection) set to 1 and no voltage input<br />

from the FV terminal will be valid in any case.<br />

9 Multi-step speed command 1<br />

10 Multi-step speed command 2<br />

11 Inching command (ON: Inching command) This command takes precedence over the<br />

frequency reference.)<br />

12 Acceleration/Deceleration time switching command (ON: Acceleration/Deceleration time<br />

2 will be used; OFF: Acceleration/Deceleration time 1 will be used)<br />

13 External baseblock command (ON: Valid)<br />

14 External baseblock command (OFF: Valid)<br />

15 Speed search command from max. frequency (ON: Speed search)<br />

16 Speed search command from set frequency (ON: Speed search)<br />

17 Parameter set-inhibit (ON: Invalid)<br />

No parameter settings other than frequency reference settings with the FREF indicator<br />

will be available if parameter set-inhibit is valid.<br />

18 Integral value of PID control reset command (ON: Integral value reset)<br />

19 PID control invalidating command (ON: The target value from the FV terminal becomes<br />

the frequency reference.)<br />

20 Timer function input (Set with n077 and n078)<br />

21 Inverter overheat warning (ON: “OH3” will be displayed and the Inverter will continue<br />

running)<br />

22 Analog frequency sample and hold (ON: Sampling and holding)<br />

23 Power OFF stop input (NO contact: Valid when NO contact is ON)<br />

24 Power OFF stop input (NC contact: Valid when NC contact is OFF)<br />

25 Up/Down command (Only n039 can be set<br />

to 25)<br />

S5 will be used for up command and S6 will be used for down command and the value<br />

set with n038 will be ignored.