Minimum Baseblock Time<br />

Setting range 0.5 to 5.0 Unit s Default setting<br />

See note<br />

Note The default-set value varies with the Inverter model.<br />

• Set with n053 time in 1-s units to start the speed search control after<br />

RUN input is ON and instantaneous power failure processing starts.<br />

Refer above for, Speed Search Command.<br />

n054<br />

V/f Characteristics During Speed Search<br />

Setting range 0 to 100 Unit % (Usual V/f<br />

characteristics<br />

ratio)<br />

Default setting<br />

See note<br />

Note The default-set value varies with the Inverter model.<br />

• Set percentage of V/f characteristics for speed search.<br />

• It is usually not necessary to change the default-set value.<br />

n055<br />

Stop Compensation Time<br />

Setting range 0.0 to 2.0 Unit s Default setting<br />

See note<br />

Note The default-set value varies with the Inverter model.<br />

• Set instantaneous power failure compensation time in 1-s units.<br />

• It is usually not necessary to change the default-set value.<br />

n056<br />

Number of Error Retries<br />

Setting range 0 to 10 Unit Times Default setting<br />

0<br />

!<br />

Caution<br />

The Inverter may be damaged if the error retry function is used.<br />

!<br />

Caution<br />

Given that the Inverter may be damaged if the error retry function is used,<br />

connect a no-fuse breaker to the Inverter and program a sequence to interrupt<br />

the operation of peripheral devices when the Inverter is error.<br />

• The error retry function permits the Inverter to restart operation automatically,<br />

even if the Inverter is error.<br />

• Use the error retry function only in case the interruption of the operation<br />

of the mechanical system is not desired, even if the Inverter may<br />

be damaged.<br />

• The error retry function is valid for the following errors. A protection<br />

function of the Inverter will work if the Inverter has any other error.<br />

OC (Overcurrent)<br />

OV (Main circuit overvoltage)<br />

UV1 (Main circuit undervoltage)<br />

GF (Ground fault)<br />

RR (Control transistor overheat)<br />

• The number of error retries counted will be cleared in the following<br />

cases.