n053<br />
Minimum Baseblock Time<br />
Setting range 0.5 to 5.0 Unit s Default setting<br />
See note<br />
Note The default-set value varies with the Inverter model.<br />
• Set with n053 time in 1-s units to start the speed search control after<br />
RUN input is ON and instantaneous power failure processing starts.<br />
Refer above for, Speed Search Command.<br />
n054<br />
V/f Characteristics During Speed Search<br />
Setting range 0 to 100 Unit % (Usual V/f<br />
characteristics<br />
ratio)<br />
Default setting<br />
See note<br />
Note The default-set value varies with the Inverter model.<br />
• Set percentage of V/f characteristics for speed search.<br />
• It is usually not necessary to change the default-set value.<br />
n055<br />
Stop Compensation Time<br />
Setting range 0.0 to 2.0 Unit s Default setting<br />
See note<br />
Note The default-set value varies with the Inverter model.<br />
• Set instantaneous power failure compensation time in 1-s units.<br />
• It is usually not necessary to change the default-set value.<br />
n056<br />
Number of Error Retries<br />
Setting range 0 to 10 Unit Times Default setting<br />
0<br />
!<br />
Caution<br />
The Inverter may be damaged if the error retry function is used.<br />
!<br />
Caution<br />
Given that the Inverter may be damaged if the error retry function is used,<br />
connect a no-fuse breaker to the Inverter and program a sequence to interrupt<br />
the operation of peripheral devices when the Inverter is error.<br />
• The error retry function permits the Inverter to restart operation automatically,<br />
even if the Inverter is error.<br />
• Use the error retry function only in case the interruption of the operation<br />
of the mechanical system is not desired, even if the Inverter may<br />
be damaged.<br />
• The error retry function is valid for the following errors. A protection<br />
function of the Inverter will work if the Inverter has any other error.<br />
OC (Overcurrent)<br />
OV (Main circuit overvoltage)<br />
UV1 (Main circuit undervoltage)<br />
GF (Ground fault)<br />
RR (Control transistor overheat)<br />
• The number of error retries counted will be cleared in the following<br />
cases.