n011<br />
Rated Input Voltage of Motor<br />
Setting range 150.0 to 255.0 Unit V Default setting<br />
200.0 (400.0)<br />
(510.0)<br />
• Set the rated input voltage of the motor according to the rated input<br />
voltage of the motor before setting the V/f pattern. This set value will<br />
be used to calculate the voltage axis of the V/f pattern.<br />
n012<br />
Maximum Frequency (FMAX)<br />
Setting range 50.0 to 400.0 Unit Hz Default setting<br />
60.0<br />
n013<br />
Setting range 0.1 to 255.0<br />
(510.0)<br />
n014<br />
Maximum Voltage (VMAX)<br />
Unit V Default setting<br />
Maximum Voltage Frequency (FA)<br />
Setting range 0.2 to 400.0 Unit Hz Default setting<br />
n015<br />
Intermediate Output Frequency (FB)<br />
Setting range 0.1 to 399.9 Unit Hz Default setting<br />
n016<br />
Setting range 0.1 to 255.0<br />
(510.0)<br />
n017<br />
Intermediate Output Frequency Voltage (VC)<br />
Unit V Default setting<br />
Minimum Output Frequency (FMIN)<br />
Setting range 0.1 to 10.0 Unit Hz Default setting<br />
200.0 (400.0)<br />
60.0<br />
3.0<br />
15.0 (30.0)<br />
1.5<br />
n018<br />
Setting range 0.1 to 50.0<br />
(100.0)<br />
Minimum Output Frequency Voltage (VMIN)<br />
Unit V Default setting<br />
Note Figures in parentheses apply to the 400-V Inverter.<br />
Optional V/f Pattern in Detail<br />
Voltage<br />
10.0 (20.0)<br />
• An optional V/f pattern will be available and n012 to n018 can be set if<br />
the V/f pattern is set to F.<br />
Frequency<br />
(Hz)