• Set with n071 and n072 current levels in 1% units based on the rated<br />
output current as 100% to enable the acceleration and operation stall<br />
prevention functions to work.<br />
Acceleration Stall Prevention<br />
Operation<br />
Stall<br />
Prevention<br />
Operation Stall Prevention<br />
Operation<br />
Stall<br />
Prevention<br />
Time<br />
Time<br />
Output<br />
frequency<br />
Output<br />
frequency<br />
The output frequency is controlled to a<br />
level to enable the Inverter to continue<br />
operating the motor without stalling.<br />
Time<br />
The output frequency is controlled to a<br />
level to enable the Inverter to continue<br />
operating the motor without stalling.<br />
Time<br />
n073<br />
Frequency Detection Level<br />
Setting range 0.0 to 400.0 Unit Hz Default setting<br />
• The parameter n073 is used to detect the output frequency.<br />
• The Inverter will output a signal as a multi-function contact output<br />
while the output frequency is higher than, lower than, or the same as<br />
the frequency set with n073.<br />
• Set n040 and n041 (i.e., multi-function contact output selection):<br />
To 3 to permit the Inverter to output a signal while the output frequency is the same as the<br />
frequency set with n073.<br />
To 4 to permit the Inverter to output a signal while the output frequency is the same as or<br />
lower than the frequency set with n073.<br />
To 5 to permit the Inverter to output a signal while the output frequency is the same as or<br />
higher than the frequency set with n073. Refer above.<br />
0.0<br />
n074<br />
Overtorque Detection Function Selection<br />
Setting range 0 to 4 Unit --- Default setting<br />
0<br />
n075<br />
Overtorque Detection Level<br />
Setting range 30 to 200 Unit % (Rated output<br />
current ratio)<br />
Default setting<br />
160<br />
n076<br />
Overtorque Detection Time<br />
Setting range 0.1 to 10.0 Unit s Default setting<br />
• The parameters n074, n075, and n076 are used to set the overtorque<br />
detection function.<br />
0.1