Note 1. Do not set n001 to any value other than the above.<br />
Note 2. Select the FV terminal to input the frequency reference within a voltage range from 0<br />
to 10 VDC or the FI terminal to input the frequency reference within a current range<br />
from 4 to 20 mA with n042.<br />
Note 3. The analog frequency reference will be retrieved as frequency reference 1 and the<br />
value set with n025 will be ignored if n002 is set to 2 or 3.<br />
Frequency references 2 to 4 set with n026 to n028 will be available if the Inverter uses<br />
multi-function input set to a multi-step speed.<br />
n003<br />
Setting range 150.0 to 255.0<br />
(510.0)<br />
Input Voltage Selection<br />
Unit --- Default setting<br />
200.0 (400.0)<br />
Note The figures in the parentheses apply to the 400-V Inverter.<br />
n004<br />
• Set the input voltage of the Inverter to determine the voltage protection<br />
level of the Inverter.<br />
Interruption Mode Selection<br />
Setting range 0 to 3 Unit --- Default setting<br />
0<br />
• Set n004 to the stop mode to be invoked when the STOP/RESET Key<br />
is pressed or when the run command is OFF.<br />
• To inhibit the Inverter from performing the next operation until the motor<br />
stops, set n004 to 2 or 3.<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 Deceleration stop<br />
1 Free running stop<br />
2 Free running stop 1 with timer. The run command during acceleration time 1 or 2 will be<br />
ignored.<br />
3 Free running stop 2 with timer. The constant run command is valid. The motor will start<br />
running after acceleration time 1 or 2 passes.<br />
Deceleration Stop (n004 = 0)<br />
Output frequency<br />
Deceleration rate determined by deceleration<br />
time 1 set with n020 or deceleration time 2<br />
set with n022.<br />
Minimum output frequency<br />
(n017)<br />
Stop DC control time (n065)<br />
Run command<br />
Free Running Stop (n004 = 1)<br />
Output frequency<br />
Motor free running<br />
Run command