Note 1. Do not set n001 to any value other than the above.<br />

Note 2. Select the FV terminal to input the frequency reference within a voltage range from 0<br />

to 10 VDC or the FI terminal to input the frequency reference within a current range<br />

from 4 to 20 mA with n042.<br />

Note 3. The analog frequency reference will be retrieved as frequency reference 1 and the<br />

value set with n025 will be ignored if n002 is set to 2 or 3.<br />

Frequency references 2 to 4 set with n026 to n028 will be available if the Inverter uses<br />

multi-function input set to a multi-step speed.<br />

n003<br />

Setting range 150.0 to 255.0<br />

(510.0)<br />

Input Voltage Selection<br />

Unit --- Default setting<br />

200.0 (400.0)<br />

Note The figures in the parentheses apply to the 400-V Inverter.<br />

n004<br />

• Set the input voltage of the Inverter to determine the voltage protection<br />

level of the Inverter.<br />

Interruption Mode Selection<br />

Setting range 0 to 3 Unit --- Default setting<br />

0<br />

• Set n004 to the stop mode to be invoked when the STOP/RESET Key<br />

is pressed or when the run command is OFF.<br />

• To inhibit the Inverter from performing the next operation until the motor<br />

stops, set n004 to 2 or 3.<br />

Set Values<br />

Set<br />

Description<br />

value<br />

0 Deceleration stop<br />

1 Free running stop<br />

2 Free running stop 1 with timer. The run command during acceleration time 1 or 2 will be<br />

ignored.<br />

3 Free running stop 2 with timer. The constant run command is valid. The motor will start<br />

running after acceleration time 1 or 2 passes.<br />

Deceleration Stop (n004 = 0)<br />

Output frequency<br />

Deceleration rate determined by deceleration<br />

time 1 set with n020 or deceleration time 2<br />

set with n022.<br />

Minimum output frequency<br />

(n017)<br />

Stop DC control time (n065)<br />

Run command<br />

Free Running Stop (n004 = 1)<br />

Output frequency<br />

Motor free running<br />

Run command