Set Values<br />

Set<br />

Description<br />

value<br />

0 Inhibits overheating protection from functioning.<br />

1 Permits overheating protection to function.<br />

n080<br />

Input Open-phase Detection Level<br />

Setting range 1 to 100 Unit (400/800 VDC<br />

as 100%)<br />

n081<br />

Input Open-phase Detection Time<br />

Default setting<br />

Setting range 2 to 255 Unit x 1.28 s Default setting<br />

7<br />

8<br />

• The parameters n080 and n081 are used to set the input phase loss<br />

detection function.<br />

• It is usually not necessary to change the default-set values.<br />

• The Inverter will not detect input phase loss if n080 is set to 100.<br />

• Set n080 of the 200-V Inverter based on 400 VDC as 100% and that of<br />

the Inverter of 400-V class based on 800 VDC as 100%.<br />

• The input phase loss detection function is used to detect the voltage<br />

ripples that will be generated from the main circuit DC power supply<br />

when input phase loss results.<br />

The Inverter will detect input phase loss if the voltage width of the voltage<br />

ripples of the main circuit DC power supply exceeds the range set<br />

with n080 for a period exceeding the time set with n081.<br />

• If the power supplied to the Inverter has ripples, set n080 or n081 to a<br />

large value so that the Inverter will not detect input phase loss.<br />

n082<br />

Output Open-phase Detection Level<br />

Setting range 0 to 100 Unit % (Rated output<br />

current ratio)<br />

n083<br />

Output Open-phase Detection Time<br />

Default setting<br />

Setting range 0.0 to 2.0 Unit s Default setting<br />

0<br />

0.2<br />

• The parameters n082 and n083 are used to set the output phase loss<br />

detection function.<br />

• The Inverter will not detect output phase loss if n082 is set to 0. The<br />

default-set value of n082 is 0.<br />

• When an output phase loss occurs, the Inverter will detect a decrease<br />

in the output current of the phase.<br />

• To use the output phase loss detection function, refer to the following<br />

procedure and set with n082 an appropriate output phase loss detection<br />

level.<br />

Start the motor with no load.<br />

Use the Digital Operator and monitor the amperage of the output current.<br />

Calculate the percentage of the output current based on the rated output current as 100%.<br />

Set n082 to half the number calculated.