Parameters in Detail<br />
Refer to the following for the functions of the parameters used with the Inverter<br />
not in energy-saving or PID control operation.<br />
n001<br />
Setting range 0, 1, 2, 3, 6,<br />
and 7<br />
Group 1:<br />
Group 2:<br />
Group 3:<br />
Parameter Write Prohibit Selection/Parameter<br />
Initialization<br />
Unit --- Default setting<br />
• The parameters used by the Inverter are classified into the following<br />
three groups.<br />
n001 to n034<br />
n035 to n049<br />
n050 to n108 (Up to n102 can be used.)<br />
• The Inverter is default-set so that only parameters of group 1 can be<br />
set and checked and the parameters of groups 2 and 3 can only be<br />
checked.<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 The parameters n001 can be set and checked and the parameters n002 to n108 can be<br />
only checked.<br />
1 The parameters of group 1 (i.e., n001 to n034) can be set and checked and the<br />
parameters of groups 2 and 3 (i.e., n035 to n049 and n050 to n108) can be only<br />
checked.<br />
2 The parameters of groups 1 and 2 can be set and checked and the parameters of group<br />
3 can be only checked.<br />
3 The parameters of groups 1, 2, and 3 can be set and checked.<br />
6 All parameters will be set to default-set values.<br />
7 All parameters will be initialized with a three-wire sequence. (see note 2)<br />
Note<br />
Note<br />
1. Do not set n001 to any value other than the above.<br />
2. Refer to n035 on below for the 3-wire sequence.<br />
n002<br />
Operation Mode Selection<br />
Setting range 0 to 3 Unit --- Default setting<br />
• The Inverter has four operation modes. Refer to the following table<br />
and select one of the modes with n002.<br />
Set Values<br />
Set<br />
value<br />
Run command Frequency reference Operation mode indicator of Digital<br />
Operator<br />
Remote operation Analog input<br />
0 Digital Operator Digital Operator Not lit Not lit<br />
1 Control circuit terminals<br />
Digital Operator Lit Not lit<br />
2 Digital Operator Control circuit terminals<br />
(see note 2)<br />
Not lit<br />
Lit<br />
3 Control circuit terminals<br />
Control circuit terminals<br />
(see note 2)<br />
Lit<br />
Lit<br />
1<br />
3