Note The acceleration time and deceleration time of the Inverter will increase by the S-shaped<br />
characteristic time set with n023.<br />
Output<br />
frequency<br />
With no S-shaped<br />
characteristic<br />
S: S-shaped characteristic time<br />
Time<br />
n024<br />
Unit of Frequency Reference<br />
Setting range 0 to 3,999 Unit --- Default setting<br />
0<br />
• Set the unit of the frequency references set or checked with the Digital<br />
Operator.<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 0.1-Hz units<br />
1 0.1% units based on the maximum frequency as 100%.<br />
2 to 39 r/min (r/min = 120 x frequency/n024<br />
Set n024 to the number of poles of the motor.<br />
40 to<br />
3,999<br />
Determine the display method of the maximum frequency set with n012. A frequency less<br />
than the maximum frequency will be displayed proportionally.<br />
Example: Set n024 to 1100 so that “10.0” will be displayed at the maximum frequency.<br />
10.0 →1100<br />
Value with no decimal point.<br />
Decimal point position<br />
n025 Frequency Reference 1<br />
Setting range<br />
0 to maximum<br />
frequency<br />
Unit Set with n024 Default setting<br />
6.0<br />
n026 Frequency Reference 2<br />
Setting range<br />
0 to maximum<br />
frequency<br />
Unit Set with n024 Default setting<br />
0.0<br />
n027 Frequency Reference 3<br />
Setting range<br />
0 to maximum<br />
frequency<br />
Unit Set with n024 Default setting<br />
0.0<br />
n028 Frequency Reference 4<br />
Setting range<br />
0 to maximum<br />
frequency<br />
Unit Set with n024 Default setting<br />
0.0<br />
• Set frequency references 1 to 4.<br />
• The multi-step speed command must be selected to use frequency<br />
references 2 to 4.