Function<br />

No.<br />

n095<br />

n096<br />

n097<br />

n098<br />

n099<br />

n100<br />

n101<br />

n102<br />

Name<br />

Energysaving<br />

control<br />

Energysaving<br />

control<br />

selection<br />

Energysaving<br />

coefficient<br />

K2<br />

Energysaving<br />

voltage<br />

lower<br />

limit for 60<br />

Hz<br />

Energysaving<br />

voltage<br />

lower<br />

limit for 6<br />

Hz<br />

Mean power<br />

time<br />

Search<br />

control voltage<br />

limit<br />

Search<br />

control voltage<br />

step<br />

when 100%<br />

Search<br />

control voltage<br />

step<br />

when 5%<br />

Description<br />

0: Inhibits the Inverter from performing<br />

energy-saving control.<br />

1: Permits the Inverter to perform energysaving<br />

control.<br />

Set coefficient so that maximum motor efficiency<br />

will be obtained.<br />

Set lower limits of energy-saving control<br />

output voltage in 1% units at 6 Hz and<br />

60 Hz based on motor rated voltage set<br />

with n011 as 100%, in which case, lower<br />

limit of energy-saving g control output voltage<br />

will be on a straight line linking values<br />

set with n097 and n098 if energy-saving<br />

control output frequency is between 6 and<br />

60 Hz.<br />

Set time to calculate mean output power<br />

of Inverter performing energy-saving control.<br />

Time (ms) = 25 x n099<br />

Set range of variable voltage in 1% units<br />

to be used by Inverter in search control<br />

mode based on rated motor input voltage<br />

as 100%.<br />

Search operation function will be invalid if<br />

n101 is set to 0.<br />

Set range of variable voltage in 1% units<br />

to be used by Inverter in search control<br />

mode with 100% search operation start<br />

voltage based on rated motor input voltage<br />

as 100%.<br />

Set range of variable voltage in 1% units<br />

to be used by Inverter in search control<br />

mode with 5% search operation start voltage<br />

based on rated motor input voltage as<br />

100%.<br />

Not used n103 Not used Do not change setting. [1]<br />

n104 Not used Do not change setting. [1]<br />

n105 Not used Do not change setting. [0]<br />

n106 Not used Do not change setting. [0]<br />

n107 Not used Do not change setting. [2]<br />

n108 Not used Do not change setting. [1]<br />

Setting<br />

range<br />

0, 1<br />

[0]<br />

0.00 to<br />

655.0<br />

[See<br />

note]<br />

0 to<br />

120<br />

[50]<br />

0 to 25<br />

[12]<br />

1 to<br />

200<br />

1<br />

0 to<br />

100<br />

0<br />

0.0 to<br />

10.0<br />

[0.5]<br />

0.0 to<br />

10.0<br />

[0.2]<br />

User<br />

setting<br />