does not save unnecessary power supply to the motor, refer to the following<br />

table to check the probable cause of the trouble and take countermeasures<br />

against the trouble.<br />

Running conditions of the motor may inhibit the Inverter from performing effective<br />

energy-saving control.<br />

Problem Probable cause Remarks<br />

Output power does not<br />

change<br />

Inverter does not perform<br />

effective energy-saving<br />

control<br />

Inverter is running at a<br />

frequency exceeding 120<br />

Hz<br />

Load factor of the motor is<br />

too large<br />

The Inverter does not save unnecessary<br />

power supply to the motor while the<br />

Inverter is running at a frequency<br />

exceeding 120 Hz.<br />

The Inverter does not perform effective<br />

energy-saving control if the load factor of<br />

the motor is too large.<br />

Reference: Energy-saving control of motor<br />

with 7.5-kW output<br />

Energy saved (W)<br />

Output frequency: 60 Hz<br />

Constantly rotating motor<br />

drops its rotation speed for<br />

a moment<br />

Motor vibrates or does not<br />

rotate smoothly when the<br />

load is light<br />

Motor stalls<br />

Motor changes its rotation<br />

speed periodically in<br />

synchronization with the<br />

mean power time<br />

Value of the<br />

energy-saving coefficient<br />

K2 is too small and the<br />

ideal output voltage<br />

calculated by the Inverter<br />

is low<br />

Mechanical system is<br />

resonating with the<br />

Inverter<br />

Output voltage is too<br />

small<br />

Speed ripples are<br />

generated by the search<br />

operation voltage change<br />

rates<br />

Load factor (%)<br />

Set K2 with n096 according to the capacity<br />

of the motor.<br />

Reset K2 to the value for the capacity of a<br />

motor one rank lower than the motor in<br />

use if the same trouble occurs after K2 is<br />

set according to the capacity of the motor.<br />

Set the mean power time with n099 to a<br />

larger value.<br />

Set the lower output voltage limits with<br />

n097 and n098 to larger values.<br />

Set the energy-saving coefficient K2 with<br />

n096 to a larger value.<br />

Reset K2 to the value for the capacity of a<br />

motor one rank lower than the motor in<br />

use if the same trouble occurs after K2 is<br />

set according to the capacity of the motor.<br />

Set the values of n101 and n102 to<br />

smaller values.<br />

Set the search operation voltage limit with<br />

n100 to 0 so that the search operation<br />

function will not work.