n027 Frequency Reference 3<br />
Setting range<br />
0 to maximum<br />
frequency<br />
Unit Set with n024 Default setting<br />
0.0<br />
n028 Frequency Reference 4<br />
Setting range<br />
0 to maximum<br />
frequency<br />
Unit Set with n024 Default setting<br />
The inching frequency reference must be set with n029 if an inching frequency is required.<br />
The inching command must be selected to use the inching frequency reference. Refer<br />
below, Multi-function Input Selection (n035 to n039) for details.<br />
0.0<br />
n029<br />
Setting range<br />
Inching Frequency Reference<br />
0 to maximum<br />
frequency<br />
Unit Set with n024 Default setting<br />
6.0<br />
Acceleration/Deceleration Time Selection (n019 to n022)<br />
Acceleration time and deceleration time can be set with n019 to n022.<br />
The acceleration/deceleration time switching command must be selected to use acceleration<br />
time 2 and deceleration time 2. Refer below, Multi-function Input Selection (n035<br />
to n039) for details.<br />
n019 Acceleration Time 1<br />
Setting range 0.0 to 3,600 Unit s Default setting<br />
n020 Deceleration Time 1<br />
Setting range 0.0 to 3,600 Unit s Default setting<br />
n021 Acceleration Time 2<br />
Setting range 0.0 to 3,600 Unit s Default setting<br />
10.0<br />
10.0<br />
10.0<br />
n022 Deceleration Time 2<br />
Setting range 0.0 to 3,600 Unit s Default setting<br />
Set Values<br />
Acceleration time: The time required for the output frequency to be 100% from 0% of the<br />
maximum frequency.<br />
Deceleration time: The time required for the output frequency to be 0% from 100% of the<br />
maximum frequency.<br />
Acceleration time 2 and deceleration time 2 is available if the acceleration/deceleration<br />
time switching command is set.<br />
Motor Rotation Direction Selection (n005 and n006)<br />
Set the rotation direction of the motor with n005 so that the motor will rotate in the set direction<br />
when the forward rotation command is input.<br />
10.0