Example of Inching Operation (Set Value: 11)<br />

Frequency<br />

reference<br />

Inching operation<br />

reference<br />

Frequency<br />

reference 1<br />

Inching operation<br />

reference<br />

Forward<br />

rotation/Stop<br />

Inching<br />

command<br />

Example of Acceleration/Deceleration Time Switching (Set Value 12)<br />

Frequency<br />

reference<br />

Acceleration<br />

time 1<br />

Deceleration<br />

time 1<br />

Acceleration<br />

time 2<br />

Deceleration<br />

time 2<br />

Maximum<br />

frequency<br />

(n012)<br />

Forward<br />

rotation/Stop<br />

Acceleration/<br />

Deceleration<br />

time switching<br />

Note The acceleration time and deceleration time of the Inverter will be switched the moment<br />

the acceleration/deceleration time switching command is input while the Inverter is accelerating<br />

or decelerating the motor.<br />

V/f Pattern Selection (n010 to n018)<br />

Set the V/f pattern according to the characteristics of the mechanical system.<br />

Set the rated input voltage of the motor with n011 according to the rated input voltage of<br />

the motor before setting the V/f pattern. This set value will be used to calculate the voltage<br />

axis of the V/f pattern.<br />

n011<br />

Setting range 150.0 to 255.0<br />

(510.0)<br />

Motor Rated Voltage<br />

Unit V Default setting<br />

200.0 (400.0)<br />

Note The figures in the parentheses apply to the 400-V Inverter.<br />

Set the V/f pattern.<br />

n010<br />

V/f Pattern Selection<br />

Setting range 0 to F Unit --- Default setting<br />

1<br />

Set Values<br />

The following two methods are available to set the V/f pattern.