Group 2: n035 to n049<br />

Function No. Name Description Setting<br />

range<br />

Sequential n035 Multi-function<br />

0 to 24 0<br />

input function<br />

input 1<br />

selection<br />

(S2)<br />

n036<br />

n037<br />

n038<br />

n039<br />

Multi-function<br />

input 2<br />

(S3)<br />

Multi-function<br />

input 3<br />

(S4)<br />

Multi-function<br />

input 4<br />

(S5)<br />

Multi-function<br />

input 5<br />

(S6)<br />

0: Reverse rotation/Stop<br />

1: Stop command (3-wire sequence<br />

selection)<br />

S3 will be used for forward/reverse<br />

rotation command and value set with<br />

n036 will be ignored.<br />

2: External error (NO contact: ON)<br />

3: External error (NC contact: ON)<br />

4: Error reset (ON: Valid)<br />

5: Operation mode selection (ON: Digital<br />

Operator; OFF: n002)<br />

6: Not used<br />

7: Emergency stop<br />

8: Analog input selection (ON: Current<br />

input through FI terminal; OFF: FV<br />

terminal)<br />

9: Multi-step speed command 1<br />

10: Multi-step speed command 2<br />

11: Inching command<br />

12: Acceleration/Deceleration time<br />

switching command<br />

13: External baseblock command (ON:<br />

Valid)<br />

14: External baseblock command (OFF:<br />

Valid)<br />

15: Speed search command from max.<br />

frequency<br />

16: Speed search command from set frequency<br />

17: Parameter set-inhibit (ON: Invalid)<br />

18: Integral value of PID control reset<br />

command<br />

19: PID control invalidating command<br />

(Set point used as frequency reference)<br />

20: Timer function input (Set with n077<br />

and n078)<br />

21: Inverter overheat warning (ON: “OH3”<br />

will be displayed)<br />

22: Analog frequency sample hold<br />

23: Power OFF stop input (NO contact)<br />

24: Power OFF stop input (NC contact)<br />

Same as n035 2 to 24 2<br />

Same as n035 2 to 24 4<br />

Same as n035 2 to 24 9<br />

0to 22: Same as n035<br />

25: Up/Down command<br />

S5 will be used for the up command,<br />

S6 will be used for the down command,<br />

and value set with n038 will be<br />

ignored.<br />

2 to 25 10<br />

Default<br />

setting