List of Parameters<br />

Group 1: n001 to n034<br />

Function No. Name Description Setting<br />

range<br />

Parameter n001<br />

0 to 7 1<br />

group<br />

selection<br />

Parameter<br />

initialization<br />

Operation<br />

mode<br />

selection<br />

Input voltage<br />

selection<br />

Interruption<br />

mode<br />

selection<br />

Motor rotation<br />

direction<br />

selection<br />

n002<br />

n003<br />

n004<br />

n005<br />

n006<br />

Parameter<br />

write prohibit<br />

selection/Parameter<br />

initialization<br />

Operation<br />

mode<br />

selection<br />

Input voltage<br />

selection<br />

(see note)<br />

Interruption<br />

mode<br />

selection<br />

Forward/<br />

Reverse<br />

rotation<br />

selection<br />

Reverse<br />

rotation-inhibit<br />

selection<br />

0: The parameters n001 can be set and<br />

checked and the parameters n002 to<br />

n108 can be only checked.<br />

The speed and direction of the Digital<br />

Operator can be set.)<br />

1: The parameters of group 1 (i.e., n001<br />

to n034) can be set and checked and<br />

the parameters of groups 2 and 3 (i.e.,<br />

n035 to n049 and n050 to n108) can be<br />

only checked.<br />

2: The parameters of groups 1 and 2 can<br />

be set and checked and the parameters<br />

of group 3 can only be checked.<br />

3: The parameters of groups 1, 2, and 3<br />

can be set and checked.<br />

Default<br />

setting<br />

6: All parameters will be set to default-set<br />

values.<br />

7: All parameters will be initialized with a<br />

three-wire sequence.<br />

Selects method to input run command and 0 to 3 3<br />

frequency reference.<br />

Run command Frequency reference<br />

0: Digital Operator Digital Operator<br />

1: Control circuit terminals Digital Operator<br />

2: Digital Operator Control circuit terminals<br />

3: Control circuit terminals Control circuit terminals<br />

Set Inverter input voltage in 1-V units. 150.0 200.0<br />

to<br />

255.0<br />

0: Deceleration stop<br />

1: Free running stop<br />

2: Free running stop 1 with timer. The run<br />

command during deceleration time 1 or<br />

2 will be ignored.<br />

3: Free running stop 2 with timer. The<br />

constant run command is valid. The<br />

motor will start running after deceleration<br />

time 1 or 2 passes.<br />

0: When the forward rotation command is<br />

input, the motor seen from the load<br />

side rotates counterclockwise.<br />

1: When the forward rotation command is<br />

input, the motor seen from the load<br />

side rotates clockwise.<br />

0: The motor can rotate in reverse.<br />

1: The motor cannot rotate in reverse.<br />

0 to 3 0<br />

0, 1 0<br />

0, 1 0<br />

Note With 400-V Inverters, the setting range upper limits and default settings are double those<br />

shown in the table.