Protective and Diagnostic Functions<br />

Errors Interrupting Inverter Output<br />

• If the Inverter detects an error, the Inverter will have an error contact<br />

output and decelerate the motor to a stop, make the motor coast to a<br />

stop, or let the motor continue rotating according to the error processing<br />

mode selected while the Digital Operator displays the status of<br />

the error.<br />

• If an error results, refer to the following and take the necessary action.<br />

• Before restarting the Inverter, take one of the following actions to reset<br />

the Inverter.<br />

Turn ON an error reset signal by setting the multi-function input parameter used by the Inverter<br />

to 4.<br />

Press the STOP/RESET Key.<br />

Turn the main circuit power supply OFF and ON.<br />

Errors and Actions Taken<br />

Data<br />

Description<br />

display<br />

%c Overcurrent (OC)<br />

The Inverter output current<br />

instantaneously exceeded the<br />

overcurrent detection level.<br />

gf Ground fault (GF)<br />

A ground fault current<br />

exceeding 50% of the rated<br />

Inverter output current flowed<br />

from the output side of the<br />

Inverter.<br />

puf Fuse pre-arcing (PUF)<br />

The fuse of the main circuit<br />

blew out.<br />

sc<br />

Load short-circuit (SC)<br />

The Inverter output or load is<br />

shorted.<br />

Cause and action<br />

The output side of the Inverter is shorted or grounded<br />

due to motor coil burnout, poor motor coil insulation, or<br />

cable damage.<br />

The load is excessive. The acceleration and deceleration<br />

time settings are too short.<br />

A special motor or a motor with a capacity exceeding the<br />

maximum output capacity of the Inverter is used.<br />

The magnetic contactor on the output side of the Inverter<br />

was opened and closed.<br />

→ Determine the cause of the error, take the necessary<br />

action, and reset the system.<br />

The output side of the Inverter is grounded due to the<br />

motor coil burnout, poor motor coil insulation, or cable<br />

damage.<br />

→ Determine the cause of the error, take the necessary<br />

action, and reset the system.<br />

The output transistor is broken, in which case replace the<br />

Inverter. The output transistor will break if the B1 or<br />

negative terminal is shorted with the T1 (U), T2 (V), or T3<br />

(W) terminal.<br />

The output side of the Inverter is shorted or grounded.<br />

→ Determine the cause of the error, take the necessary<br />

action, and reset the system.<br />

The output side of the Inverter is shorted or grounded<br />

due to motor coil burnout, poor motor coil insulation, or<br />

cable damage.<br />

→ Determine the cause of the error, take the necessary<br />

action, and reset the system.