List of Parameters<br />
Values in brackets [ ] are default-set values.<br />
Group 1: n001 to n034<br />
Function No. Name Description Setting<br />
range<br />
Parameter n001<br />
0 to 7<br />
group<br />
selection<br />
Parameter<br />
initialization<br />
Operation<br />
mode<br />
selection<br />
Input voltage<br />
selection<br />
Interruption<br />
mode<br />
selection<br />
Motor rotation<br />
direction<br />
selection<br />
n002<br />
n003<br />
n004<br />
n005<br />
n006<br />
Parameter<br />
write prohibit<br />
selection/Parameter<br />
initialization<br />
Operation<br />
mode<br />
selection<br />
Input voltage<br />
selection<br />
(see note)<br />
Interruption<br />
mode<br />
selection<br />
Forward/<br />
Reverse<br />
rotation<br />
selection<br />
Reverse<br />
rotation-inhibit<br />
selection<br />
0: The parameters n001 can be set and<br />
checked and the parameters n002 to<br />
n108 can be only checked.<br />
The speed and direction of the Digital<br />
Operator can be set.)<br />
1: The parameters of group 1 (i.e., n001<br />
to n034) can be set and checked and<br />
the parameters of groups 2 and 3 (i.e.,<br />
n035 to n049 and n050 to n108) can be<br />
only checked.<br />
2: The parameters of groups 1 and 2 can<br />
be set and checked and the parameters<br />
of group 3 can only be checked.<br />
3: The parameters of groups 1, 2, and 3<br />
can be set and checked.<br />
6: All parameters will be set to default-set<br />
values.<br />
7: All parameters will be initialized with a<br />
three-wire sequence. [1]<br />
Selects method to input run command and 0 to 3<br />
frequency reference.<br />
Run command Frequency reference<br />
0: Digital Operator Digital Operator<br />
1: Control circuit terminals Digital Operator<br />
2: Digital Operator Control circuit terminals<br />
3: Control circuit terminals Control circuit terminals [3]<br />
Set Inverter input voltage in 1-V units. 150.0<br />
to<br />
255.0<br />
[200.0]<br />
0: Deceleration stop<br />
0 to 3<br />
1: Free running stop<br />
2: Free running stop 1 with timer. The run<br />
command during deceleration time 1 or<br />
2 will be ignored.<br />
3: Free running stop 2 with timer. The<br />
constant run command is valid. The<br />
motor will start running after deceleration<br />
time 1 or 2 passes.<br />
[0]<br />
0: When the forward rotation command is 0, 1<br />
input, the motor seen from the load<br />
side rotates counterclockwise.<br />
1: When the forward rotation command is<br />
input, the motor seen from the load<br />
side rotates clockwise.<br />
[0]<br />
0: The motor can rotate in reverse. 0, 1<br />
1: The motor cannot rotate in reverse.<br />
[0]<br />
User<br />
setting<br />
Note With 400-V Inverters, the setting range upper limits and default settings are double those<br />
shown in the table.