Function No. Name Description Setting<br />

range<br />

Slip compensation<br />

Motor rated<br />

0.0 to<br />

slip<br />

9.9<br />

Others<br />

n109<br />

(see<br />

note 1)<br />

n110<br />

(see<br />

note 1)<br />

n111<br />

(see<br />

note 1)<br />

n112<br />

(see<br />

note 1)<br />

n113<br />

(see<br />

note 1)<br />

n114<br />

(see<br />

note 1)<br />

n115<br />

(see<br />

note 1)<br />

Motor noload<br />

current<br />

Slip compensation<br />

primary<br />

delay time<br />

Operation<br />

selection<br />

when Digital<br />

Operator<br />

is disconnected<br />

Frequency<br />

detection<br />

width<br />

Local/Remote<br />

Key<br />

selection<br />

Sets the motor rated slip in % units of motor<br />

rated frequency when slip compensation<br />

is used.<br />

Sets the motor no-load current in % units<br />

of motor rated current (n032).<br />

Slip compensation primary delay time is<br />

set in s units.<br />

Note Usually setting is not necessary. Adjust<br />

when slip compensation responsiveness<br />

is low or when speed has<br />

not stabilized.<br />

When responsiveness is low, decrease<br />

the set value.<br />

When speed has not stabilized, increase<br />

the set value.<br />

Sets the operation when the Digital Operator<br />

is disconnected.<br />

0: Disabled (operation continues even if<br />

the Digital Operator is disconnected.)<br />

1: Enabled (CPF0 or CPF1 is detected<br />

with Digital Operator. Inverter output<br />

will be cut off and error contact will be<br />

operated.)<br />

Sets the width of frequency agreement<br />

(n040, n041) and frequency detection<br />

(n073) in Hz units.<br />

Used to set the Operation mode by switching<br />

to the Remote mode using the Local/<br />

Remote Key.<br />

0: Run signals that are input during mode<br />

switching are ignored. (Input Run signals<br />

after switching the mode.)<br />

1: Run signals become effective immediately<br />

after switching to the Remote<br />

mode.<br />

For the manufacturer’s use. (Do not set.)<br />

0 to 99 30<br />

0.0 to<br />

25.5<br />

0, 1 0<br />

0.0 to<br />

25.5<br />

0, 1 0<br />

See<br />

note 2<br />

Default<br />

setting<br />

0.0<br />

2.0<br />

2.0<br />

See<br />

note 2<br />

Note<br />

Note<br />

1. These constants are disabled for 1010 to 1015 of PROM number (U-10).<br />

2. Setting ranges and default settings vary with the Inverter model.