Note<br />

speed motors (e.g., spindle motors) or any other motor that has an efficiency curve<br />

with more than one peak (e.g., any double squirrel-cage motor).<br />

2. The Inverter performs energy-saving control at 15 to 120 Hz. The Inverter does not<br />

perform energy-saving control at a frequency exceeding 120 Hz.<br />

n100<br />

Search Control Voltage Limit<br />

Setting range 0 to 100 Unit % (Rated input<br />

voltage ratio of<br />

motor)<br />

Default setting<br />

0<br />

Set Values<br />

Set the range of the variable voltage of the Inverter in search operation mode with 1%<br />

units based on the rated input voltage of the motor set with n011 as 100%.<br />

The value of n100 is usually set to a range from 0 to 20%. Usually n100 is set to 10%.<br />

The search operation will not be available if n100 is set to 0.<br />

n097<br />

Energy-saving Voltage Lower Limit for 60 Hz<br />

Setting range 0 to 120 Unit % (Rated input<br />

voltage ratio of<br />

motor)<br />

n098<br />

Default setting<br />

Energy-saving Voltage Lower Limit for 6 Hz<br />

Setting range 0 to 25 Unit % (Rated input<br />

voltage ratio of<br />

motor)<br />

Default setting<br />

50<br />

12<br />

Set Values<br />

Set the lower output voltage limits of the Inverter in energy-saving mode.<br />

It is usually unnecessary to change the default-set values of n097 and n098.<br />

The parameters n097 and n098 set the lower output voltage limits of the Inverter to prevent<br />

the motor from stalling.<br />

Set n097 and n098 to values 5% to 10% larger than the default-set values if the motor<br />

stalls.<br />

Output voltage lower limit (%)<br />

n099<br />

Mean Power Time<br />

Setting range 1 to 200 Unit x 25 ms Default setting<br />

1<br />

Set Values<br />

Set time to calculate the mean output power of the Inverter in energy-saving mode.<br />

It is usually not necessary to change the default-set value of n099.