16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

20.70 CHAPTER TWENTY<br />

5. Sensible cooling process sf-s due to the heat loss from the warm <strong>air</strong> inside the supply duct<br />

through the duct wall to the ambient <strong>air</strong> qsd. 6. Space <strong>conditioning</strong> process sr. During heating mode operation in winter, heat is supplied to the<br />

space to compensate for the transmission loss, <strong>and</strong> moisture is absorbed by the supply <strong>air</strong> due to<br />

the space latent load. Supply <strong>air</strong> at point s is then changed to r.<br />

The heat supplied to the conditioned space to <strong>of</strong>fset the space heating load Qrh, in Btu/h (W),<br />

can be calculated as<br />

Qrh � 60 V˙ s�scpa(Ts � Tr) (20.86)<br />

And the latent heat absorbed by the supply <strong>air</strong> Qrl, in Btu/h (W), is<br />

(20.87)<br />

Example 20.6. For the same constant-volume single-zone system as that in Example 20.4, shown<br />

in Fig. 20.22, the following winter design conditions are given:<br />

Winter outdoor design conditions:<br />

Dry-bulb temperature 15°F (9.4°C)<br />

Relative humidity 30 percent<br />

Winter indoor design temperature 72°F (22.2°C)<br />

Outdoor <strong>air</strong> requirement 3200 cfm (1510 L/s)<br />

Temperature rise:<br />

Due to heat release from light fixtures 2°F (1.11°C)<br />

Return fan power heat gain 1°F (0.56°C)<br />

Supply fan 2°F (1.11°C)<br />

Temperature drop <strong>of</strong> the supply duct 1°F (0.56°C)<br />

Space heating load 225,000 Btu/h (65,925 W)<br />

Space latent load 60,000 Btu/h (17,580 W)<br />

Supply volume flow rate 21,140 cfm (9976 L/s)<br />

Determine<br />

1. The space relative humidity at winter design conditions<br />

2. The temperature <strong>of</strong> supply <strong>air</strong><br />

3. The heating coil load<br />

Solution<br />

Q rl � 60V˙ s� s(w r � w s)h fg,32<br />

1. To develop a winter heating mode <strong>air</strong> <strong>conditioning</strong> cycle for a constant-volume single-zone<br />

system, the space humidity ratio wr must be determined. Because the winter indoor temperature is<br />

given, the space relative humidity can then be found from the psychrometric chart.<br />

Assume that the moist volume <strong>of</strong> the warm supply <strong>air</strong> vs � 13.75 ft3 /lb (0.86 m3 /kg). Because<br />

�s � 1/vs, from Eq. (20.87)<br />

w r � w s �<br />

Q rl<br />

60V˙ s � s h fg,32<br />

60,000 � 13.75<br />

�<br />

60 � 21,140 � 1075<br />

� 0.000605 lb / lb

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!