16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

11.42 CHAPTER ELEVEN<br />

(2048 kPa abs.), <strong>and</strong> the suction pressure is 91�3 � 88 psia (607 kPa abs.) with a suction temperature<br />

<strong>of</strong> 45°F (7.2°C). A 10 to 12°F (5.6 to 6.7°C) superheat at the outlet <strong>of</strong> the DX coil is considered<br />

suitable. Then at an outdoor <strong>air</strong> temperature <strong>of</strong> 95°F (35°C), if the discharge/suction pressure<br />

<strong>of</strong> the operating <strong>air</strong>-cooled DX system is around 282/73 psig (1944/503 kPag) <strong>and</strong> the superheat is<br />

between 10 <strong>and</strong> 12°F (5.6 to 6.7°C), the refrigerant charge is considered all right.<br />

Minimum Performance <strong>and</strong> Equipment Selection<br />

ASHRAE/IESNA St<strong>and</strong>ard 90.1-1999 m<strong>and</strong>ates the minimum efficiency requirements <strong>of</strong> <strong>air</strong>cooled,<br />

water-cooled, <strong>and</strong> evaporatively cooled packaged units for direct-expansion reciprocating<br />

<strong>and</strong> scroll <strong>refrigeration</strong> systems. The requirements are expressed in terms <strong>of</strong> energy efficiency ratio<br />

(EER) <strong>and</strong> integrated part-load value (IPLV) as listed in Table 11.6. When multiple rating conditions<br />

or performance requirements are provided, the equipment shall satisfy all stated requirements<br />

unless otherwise exempted. The selected <strong>air</strong>-cooled packaged unit should meet the minimum performance<br />

guidelines at both design <strong>and</strong> part-load operation.<br />

11.9 ROTARY REFRIGERATION SYSTEMS<br />

Rotary Compressor<br />

Rotary <strong>refrigeration</strong> systems using rotary compressors are widely adopted in small <strong>refrigeration</strong><br />

systems such as refrigerators, room <strong>air</strong> conditioners, <strong>and</strong> room heat pumps having a cooling capacity<br />

from a fraction <strong>of</strong> a horsepower to about 4 hp (� 0.75 kW to 3.0 kW).<br />

The rolling-piston rotary compressor, shown in Fig. 11.24, is the most widely used rotary compressor<br />

in small <strong>refrigeration</strong> systems today. A rolling piston is mounted on an eccentric shaft, <strong>and</strong> a<br />

FIGURE 11.24 A rolling-piston rotary compressor.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!