16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Controls<br />

AIR SYSTEMS: FAN COMBINATION AND SMOKE CONTROL 22.21<br />

Point o Point m Paint r Point ru<br />

p, in. WG<br />

V<br />

0 � 0.6 � 0.03 1.0<br />

· , cfm 20,000 20,000 20,000 16,650<br />

During <strong>air</strong> economizer mode, if the total pressure loss <strong>of</strong> the return system is increased to 0.70<br />

in. WC (174 Pa) <strong>and</strong> the return <strong>air</strong> is exhausted through the return fan <strong>and</strong> exhaust damper, at 50<br />

percent <strong>of</strong> design volume flow, then the fan total pressure <strong>of</strong> the return fan is<br />

�p ret.f50 �� 9650<br />

20,000� 2<br />

(0.70 � 1.0) � 0.03 � 0.37 in. WC (91 Pa)<br />

<strong>and</strong> the pressure-volume characteristics at the key points are as follows:<br />

Point o Point m Point r Point ru<br />

p, in. WG<br />

V<br />

0 � 0.15 � 0.03 0.23<br />

· , cfm 10,000 10,000 10,000 9650<br />

As in the supply <strong>and</strong> relief fan combinations, the controls for supply <strong>and</strong> return fan combination<br />

systems operated at minimum outdoor <strong>air</strong> recirculating mode <strong>and</strong> <strong>air</strong> economizer mode operations<br />

are discussed in Chap. 23.<br />

22.7 COMPARISON OF THREE FAN COMBINATION SYSTEMS<br />

An <strong>air</strong> system with supply <strong>and</strong> exhaust fan combination is simpler <strong>and</strong> less expensive. Such a system<br />

is not suitable for operation in <strong>air</strong> economizer mode for a high space pressure. In a supply <strong>and</strong><br />

exhaust fan combination, a comparatively lower pressure drop in the return system is necessary to<br />

prevent an unacceptable low pressure in the mixed plenum, such as p m ��1 in. WG (� 250 Pag).<br />

Such low mixed plenum pressure induces <strong>air</strong> leakage <strong>and</strong> may impede minimum outdoor <strong>air</strong><br />

control.<br />

The operating characteristics <strong>of</strong> the supply <strong>and</strong> relief fan combination <strong>and</strong> the supply <strong>and</strong> return<br />

fan combination can be compared as follows:<br />

● In a supply <strong>and</strong> relief fan combination in recirculating mode, total pressure at point ru may be<br />

negative; in a supply <strong>and</strong> return fan combination, total pressure at ru must be positive, in order to<br />

overcome the pressure loss <strong>of</strong> the exhaust passage.<br />

● With a relief fan, the mixed plenum pressure p m is always negative. With a return fan, p m may be<br />

positive if the return fan is too large. A positive p m means that there will be no outdoor <strong>air</strong> intake<br />

into the mixing box. Such a condition should never occur.<br />

● When a negative space pressure must be maintained, a relief fan causes the pressure in the mixed<br />

plenum to be smaller (more negative) than a return fan during minimum outdoor <strong>air</strong> recirculating<br />

mode.<br />

● When there is a considerable pressure drop in the exhaust or relief flow passage, a return fan requires<br />

high positive pressure at point ru, so energy is wasted across the recirculating damper.<br />

● A supply <strong>and</strong> relief fan combination with a lower total pressure loss return system is <strong>of</strong>ten more<br />

energy-efficient than a supply <strong>and</strong> return fan combination during recirculating mode operation,<br />

for the following reasons: (1) The pressure drop across the recirculating damper is smaller.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!