System Characteristics<br />

AC SYSTEMS: CENTRAL SYSTEMS AND CLEAN-ROOM SYSTEMS 30.13<br />

Cost <strong>and</strong> Electric Dem<strong>and</strong>s. The actual bidding price <strong>of</strong> the HVAC&R system for this project was<br />

approximately $9 million, or $8.57 per ft 2 ($92.2 per m 2 ) gross area. Compared with the originally<br />

proposed conventional <strong>air</strong> <strong>conditioning</strong> system using centrifugal chillers, the <strong>air</strong> system power input<br />

was reduced from 1679 to 1136 kW, <strong>and</strong> the electricity dem<strong>and</strong> dropped from 5960 to 4330 kW. The<br />

estimated total annual energy consumption per ft 2 gross area was 33,190 Btu/ft 2 �yr (105<br />

kWh/m 2 �yr).<br />

System charateristics <strong>of</strong> fan-powered VAV central systems are listed in Table 30.2.<br />

TABLE 30.2 System Characteristics for Fan-Powered VAV Central Systems (FPVAVCS) <strong>and</strong> Clean-Room Systems<br />

FPVAVCS CRS<br />

Zone thermal <strong>and</strong> sound control<br />

Control zone Multizone Single or multizone<br />

Control methods DDC DDC, or electric<br />

Control modes PI or PID PI or PID<br />

Heating-cooling mode changeover Automatic Cooling mode year-round,<br />

summer-winter mode<br />

changeover, automatic<br />

Sound control<br />

Indoor <strong>air</strong> quality (IAQ)<br />

35–45 dBA NC 50–65<br />

Minimum ventilation control DCV or MPC Constant-volume<br />

Filters Medium to high efficiency HEPA or ULPA with prefilters<br />

Humidity control Optional Dew point control<br />

Humidifiers<br />

Air system<br />

Steam, or heating element<br />

Types VAV <strong>air</strong> mixing MAU <strong>and</strong> RAU <strong>conditioning</strong> <strong>and</strong> mixing<br />

Supply fan Forward, or <strong>air</strong>foil centrifugal Centrifugal or vane-axial<br />

Supply fan total pressure 4.5–5.5 in. WC MAU 4–4.5 in. WC, RAU 2–2.5 in. WC<br />

Combined fan-motor-drive efficiency 55% MAU 55%, RAU 55%<br />

Relief/return fan Centrifugal or axial Centrifugal or axial<br />

Relief/return fan total pressure Relief 0.6 in. WC, return 0.5–1 in. WC Return 0.5–1 in. WC<br />

Combined fan-motor-drive efficiency 35–40% 35–40%<br />

Fan-powered VAV box fan Centrifugal, forward N/A<br />

Box fan total pressure 0.5 in. WC<br />

Combined fan-motor-drive efficiency 25%<br />

Air economizer<br />

Cooling systems<br />

Fixed or differential dry-bulb or<br />

enthalpy<br />

N/A<br />

Refrigeration compressor Centrifugal or screw Centrifugal or screw<br />

Refrigerants HCFC-123, HCFC-22, HFC-134a HCFC-123, HCFC-22, HFC-134a<br />

Evaporator Flooded liquid cooler Flooded liquid cooler<br />

Condenser Water cooled or evaporatively cooled Water cooled or evaporatively cooled<br />

Energy performance (compressor) 0.5–0.7 kW/ton 0.5–0.7 kW/ton<br />

Heating system Hot water coil, or electric heater Space, year-round cooling,<br />

preheating—outdoor <strong>air</strong>,<br />

reheating—part load; hot water,<br />

electric heating<br />

Boiler AFUE<br />

Maintenance<br />

Conventional 78%, condensing 93% Conventional 78%, condensing 93%<br />

Fault detection <strong>and</strong> diagnostics AHU, chiller AHU, chiller, filters