16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

22.36 CHAPTER TWENTY-TWO<br />

The pressure difference across the closed st<strong>air</strong>well door is 0.1 in. WC (25 Pa). The pressure differences<br />

between the st<strong>air</strong>well <strong>and</strong> the outdoors on floors other than the fire floor whose st<strong>air</strong>well<br />

doors remain open are also 0.1 in. WC (25 Pa), because the pressure drop <strong>of</strong> the open st<strong>air</strong>well door<br />

is ignored. Determine the volume flow rates <strong>of</strong> the zone smoke control <strong>and</strong> st<strong>air</strong>well pressurization<br />

systems.<br />

Solution<br />

1. The volume flow rate <strong>of</strong> the zone smoke exhaust system from the fire floor V˙ ex at a rate <strong>of</strong> 6<br />

ach is<br />

The volume flow rate <strong>of</strong> <strong>air</strong> supplied to the floors immediately above <strong>and</strong> below the fire floor is<br />

12,000 cfm (5663 L/s).<br />

2. The volume flow rate <strong>of</strong> <strong>air</strong> that is discharged through the open st<strong>air</strong>well door to the fire floor<br />

, in cfm (L/s), <strong>and</strong> is exhausted through the zone smoke control system is<br />

V˙ fire<br />

3. The volume flow rate discharged from the first-floor exit door is assumed to be the same as<br />

that from the open st<strong>air</strong>well door on the fire floor (6300 cfm, or 2973 L/s).<br />

4. From the given data, the leakage area on the st<strong>air</strong>well wall, including cracks around the st<strong>air</strong>well<br />

door, is<br />

A leak � 0.25 � 0.00011 � 600 � 0.32 ft 2<br />

If the pressure difference across the closed st<strong>air</strong>well door is 0.1 in. WC, from Eq. (22.10), the <strong>air</strong><br />

leakage rate V˙ leak through the cracks <strong>of</strong> the st<strong>air</strong>well wall on each floor whose st<strong>air</strong>well door is<br />

closed can be calculated:<br />

5. It is possible that the fire floor <strong>and</strong> the pressurized floors immediately above <strong>and</strong> below are all<br />

in the lower 10 floors. Because <strong>of</strong> the stack effect in this 20-story building, <strong>air</strong> mixed with hot gas<br />

from the burning fire is discharged from the upper 10 stories.<br />

In a 20-story building, assume that there are four open st<strong>air</strong>well doors. One is on the fire floor,<br />

<strong>and</strong> another is the first-floor exit door. Then the remaining two opened st<strong>air</strong>well doors should each<br />

discharge a combined <strong>air</strong> path that may be a combination <strong>of</strong> six parallel paths, as shown in<br />

Fig. 22.9.<br />

a-b-o<br />

a-c-d-o<br />

a-c-e-f-o<br />

a-g-h-o<br />

a-g-i-j-o<br />

a-k-l-o<br />

V˙ ex � 6 � 10,000 � 10<br />

60<br />

V˙ fire � v crit A door � 300 � 3 � 7 � 6300 cfm (2973 L/s)<br />

V˙ leak � 2610 A(�p) 1/2 � 2610 � 0.32(0.1) 1 / 2 � 264 cfm (125 L / s)<br />

6. The leakage area for the external wall for each floor is<br />

� 10,000 cfm (4719 L / s)<br />

A leak � 4800 � 0.00021 � 1.0 ft 2<br />

The leakage area for a floor area <strong>of</strong> 10,000 ft2 is<br />

Aleak � 10,000 � 0.000052 � 0.52 ft2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!