16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

30.20 CHAPTER THIRTY<br />

temperature is still at 46°F (7.8°C) or above, the discharge <strong>air</strong> temperature sensor T2 detects the fall<br />

in T dis <strong>and</strong> the DDC controller modulates the two-way valve <strong>of</strong> the chilled water cooling coil in the<br />

MAU to reduce its water flow until a 47.5°F (8.6°C) discharge <strong>air</strong> temperature <strong>and</strong> a discharge <strong>air</strong><br />

dew point <strong>of</strong> 46°F (7.8°C) are maintained.<br />

If the space sensible cooling load falls below the design load, the space temperature drops accordingly.<br />

As the space temperature sensor T1 detects such a fall in temperature, the DDC controller<br />

modulates the two-way valve <strong>of</strong> the sensible cooling coil in the RAU, reduces its water flow,<br />

<strong>and</strong> tends to maintain a constant space temperature <strong>of</strong> T r � 69°F (20.6°C).<br />

In addition to the MAU discharge <strong>air</strong> temperature <strong>and</strong> space temperature controls, there are controls<br />

for space humidity, space pressurization, filter pressure drop monitoring, <strong>and</strong> smoke detection.<br />

Because the discharge <strong>air</strong> dew point from the MAU is 46°F (7.8°C), the space dew point is also<br />

46°F (7.8°C), <strong>and</strong> the mixture <strong>of</strong> recirculating <strong>and</strong> makeup <strong>air</strong> still has a dew point <strong>of</strong> 46°F (7.8°C).<br />

After sensible cooling in the RAU, the dew point <strong>of</strong> supply <strong>air</strong>, point s, remains at 46°F (7.8°C). Because<br />

the sensible heat ratio <strong>of</strong> the space <strong>conditioning</strong> line SHR s � 0.99, the space relative humidity<br />

will be always around 42.5 percent if the space temperature T r is maintained at 69°F (20.6°C).<br />

For a space like a clean room having only a negligible latent load, supply <strong>air</strong> dew-point control<br />

can always maintain both space temperature <strong>and</strong> relative humidity within required limits by means<br />

<strong>of</strong> sensible cooling <strong>and</strong> reheating when the space sensible cooling load is varied.<br />

In Fig. 30.1a, there is a pressure sensor P1 in the clean room. This sensor measures the pressure<br />

differential �p r between the clean room <strong>and</strong> the surrounding area. This pressure differential is generally<br />

maintained at 0.05 in. WC (12.5 Pa) to prevent infiltration <strong>of</strong> contaminated <strong>air</strong>.<br />

According to the signal from P1, the DDC controller modulates the opening <strong>of</strong> the interlocked<br />

makeup <strong>air</strong> <strong>and</strong> recirculating dampers. When there is an increase in makeup <strong>air</strong> <strong>and</strong> a decrease in<br />

recirculating <strong>air</strong> in the mixing box <strong>of</strong> RAU, the space pressure differential tends to rise. A decrease<br />

in makeup <strong>air</strong> <strong>and</strong> an increase in recirculating <strong>air</strong> cause a drop in space pressure differential. The<br />

supply <strong>of</strong> makeup <strong>air</strong> is balanced by the process exhaust <strong>air</strong> <strong>and</strong> the exfiltrated <strong>air</strong> from door gaps<br />

due to the pressure differential.<br />

Pressure sensors are also used for MERV 8 prefilters, HEPA filters, <strong>and</strong> ULPA filters. If the<br />

pressure drop exceeds a predetermined limit, an indicating lamp flashes or an alarm is energized.<br />

Both signals call for replacement.<br />

When the smoke detector is energized, a signal is sent to the building fire control system. The<br />

fire alarm <strong>and</strong> the smoke control system are energized accordingly.<br />

Winter Mode Operation <strong>and</strong> Controls<br />

When the dew point <strong>of</strong> the outdoor <strong>air</strong> T o� is 44 °F (6.7°C) or below, the clean-room system is in<br />

winter mode operation. If T o��44°F (6.7°C) <strong>and</strong> T o � 53.5°F (11.9°C), the outdoor <strong>air</strong> is preheated<br />

at the preheating coil to a temperature T ph � 53.5°F (11.9°C). After absorbing the fan heat<br />

<strong>of</strong> the MAU, it enters the RAU at a discharge temperature T dis � 55°F (12.8°C). If T o��44°F<br />

(6.7°C) <strong>and</strong> T o � 53.5°F (11.9°C), the outdoor <strong>air</strong> is sensibly cooled to 53.5°F (11.9°C). Again, it is<br />

discharged to the RAU at T dis � 55°F (12.8°C) after absorbing fan heat.<br />

If makeup <strong>air</strong> at a temperature <strong>of</strong> 55°F (12.8°C) <strong>and</strong> a dew point <strong>of</strong> 44°F (6.7°C) is mixed with<br />

winter mode recirculating <strong>air</strong> <strong>of</strong> temperature 69°F (20.6°C) <strong>and</strong> 40 percent relative humidity (a dew<br />

point <strong>of</strong> 44°F, or 6.7°C), the resulting mixture will be at a temperature <strong>of</strong> 67.5°F (19.7°C). The dew<br />

point will still be 44°F (6.7°C). If the mixture is cooled at the sensible cooling coil to 62.5°F<br />

(16.9°C) according to the signal <strong>of</strong> the temperature sensor T1, <strong>and</strong> if it is supplied to the clean room<br />

at a temperature <strong>of</strong> 63.5°F (17.5°C) <strong>and</strong> a dew point <strong>of</strong> 44°F (6.7°C) after absorbing the fan heat <strong>of</strong><br />

RAU, then it will maintain a space temperature T r � 69°F (20.6°C), � r � 40 percent, <strong>and</strong> a dew<br />

point <strong>of</strong> 44°F (6.7°C) at a maximum space sensible cooling load <strong>of</strong> 563,000 Btu/h (164,960 W). A<br />

lower space sensible cooling load results in a decrease in the space temperature T r. As the sensible<br />

cooling capacity at the cooling coil is modulated <strong>and</strong> reduced by the DDC controller, the space temperature<br />

will still be maintained at 69°F (20.6°C).<br />

If T o��44°F (6.7°C), space relative humidity � r may be less than 40 percent. When the space

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!