19.8 CHAPTER NINETEEN<br />

TABLE 19.3 Sound Attenuation (Insertion Loss) for Straight Lined Sheet-Metal Rectangular Ducts, Lining<br />

Thickness 1 in.<br />

Octave <strong>and</strong> center frequency, Hz<br />

Internal<br />

cross-sectional<br />

63 125 250 500 1000 2000 4000 8000<br />

dimensions, in. Attenuation, dB/ft<br />

8 � 8 0.77 0.90 1.29 2.57 6.23 5.94 3.49 2.42<br />

8 � 18 0.60 0.67 1.04 2.22 5.10 4.72 3.06 2.26<br />

12 � 12 0.56 0.60 0.96 2.09 4.70 4.29 2.90 2.20<br />

12 � 24 0.50 0.48 0.79 1.81 3.85 3.41 2.54 2.06<br />

18 � 18 0.40 0.43 0.74 1.70 3.54 3.10 2.41 2.00<br />

18 � 36 0.30 0.32 0.59 1.47 2.90 2.46 2.11 1.87<br />

24 � 24 0.30 0.32 0.59 1.47 2.90 2.46 2.11 1.87<br />

24 � 48 0.23 0.24 0.47 1.27 2.37 1.95 1.85 1.76<br />

36 � 36 0.21 0.21 0.43 1.20 2.19 1.78 1.75 1.71<br />

36 � 72 0.16 0.16 0.34 1.03 1.79 1.41 1.54 1.60<br />

48 � 48 0.16 0.16 0.34 1.03 1.79 1.41 1.54 1.60<br />

48 � 72 0.14 0.13 0.29 0.94 1.58 1.22 1.42 1.54<br />

1. Based on measurements <strong>of</strong> surface-coated duct liners <strong>of</strong> 1.5 to 3 lb/ft 3 density. For the specific materials tested, liner density<br />

had a minor effect over the nominal range <strong>of</strong> 1.5 to 3 lb/ft 3 .<br />

2. Add natural attenuation (Table 19.1) to obtain total attenuation.<br />

Source: Abridged with permission from ASHRAE <strong>H<strong>and</strong>book</strong> 1995, HVAC Applications.<br />

TABLE 19.4 Lined Flexible Duct Insertion Loss<br />

Insertion loss dB<br />

Diameter, Length,<br />

Octave b<strong>and</strong> center frequency, Hz<br />

in. ft 63 125 250 500 1000 2000 4000<br />

8 12 8 11 21 33 37 37 24<br />

9 6 8 16 25 28 28 18<br />

6 4 6 11 17 19 19 12<br />

3 2 3 5 8 9 9 6<br />

9 12 8 11 22 33 37 36 22<br />

9 6 8 17 25 28 27 17<br />

6 4 6 11 17 19 18 11<br />

3 2 3 6 8 9 9 6<br />

10 12 8 10 22 32 36 34 21<br />

9 6 8 17 24 27 26 16<br />

6 4 5 11 16 18 17 11<br />

3 2 3 6 8 9 9 5<br />

12 12 7 9 20 30 34 31 18<br />

9 5 7 15 23 26 23 14<br />

6 3 5 10 15 17 16 9<br />

3 2 2 5 8 9 8 5<br />

14 12 5 7 16 27 31 27 14<br />

9 4 5 12 20 23 20 11<br />

6 3 4 8 14 16 14 7<br />

3 1 2 4 7 8 7 4<br />

Source: ASHRAE <strong>H<strong>and</strong>book</strong> 1995, HVAC Applications. Reprinted with permission.