16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

10.26 CHAPTER TEN<br />

Part-Load Operation<br />

Condenser Capacity. Parameters that influence the condenser capacity Q rej <strong>of</strong> a shell-<strong>and</strong>-tube condenser<br />

are mainly U o, A o, �T m, <strong>and</strong> Q rej/A o. Size <strong>and</strong> capacity <strong>of</strong> the condenser must be matched with<br />

the evaporator <strong>and</strong> compressor. Condenser capacity is always rated at certain operating conditions.<br />

When the heat flux Q rej/A o reduces at the condensing surface <strong>of</strong> the shell-<strong>and</strong>-tube condenser during<br />

part-load operation, h con increases. Therefore, the reduction <strong>of</strong> Q rej at part-load operation in a shell<strong>and</strong>-tube<br />

condenser is mainly caused by the drop in condensing temperature T con <strong>and</strong>, therefore, a<br />

smaller �T m between refrigerant <strong>and</strong> condenser water. At part-load operation, the degree <strong>of</strong> subcooling<br />

is also reduced because <strong>of</strong> the drop in condensing temperature T con.<br />

10.7 AIR-COOLED CONDENSERS<br />

Construction <strong>of</strong> Air-Cooled Condenser<br />

Air-cooled condensers use <strong>air</strong> to extract the latent heat <strong>of</strong> condensation released by the refrigerant<br />

during condensation. An <strong>air</strong>-cooled condenser generally consists <strong>of</strong> a condenser coil in which there<br />

are a main condensing coil section <strong>and</strong> a subcooling coil section connected in series, with several refrigerant<br />

circuits to condense the gaseous refrigerant to liquid, <strong>and</strong> a subcooled refrigerant at a lower<br />

level, as shown in Fig. 10.11. The condenser coil is usually equipped with copper tubes <strong>and</strong> aluminum<br />

fins when halocarbon is used as refrigerant. The diameters <strong>of</strong> the tubes are usually between<br />

1 �4<br />

3 <strong>and</strong> �4 in. (6.5 <strong>and</strong> 19 mm), <strong>and</strong> the fin spacing is generally 12 to 20 fins/in. (1.3 to 2 fins/mm).<br />

On the inner surface <strong>of</strong> the copper tubes, micr<strong>of</strong>ins (typically 60 fins/in. or a fin spacing <strong>of</strong> 0.4 mm)<br />

with a height <strong>of</strong> 0.008 in. (0.2 mm) are used, as in DX coils. The condenser coil usually has two to<br />

three rows <strong>of</strong> tubes because <strong>of</strong> the lower <strong>air</strong>-side pressure drop provided by the propeller fan.<br />

Hot gas from the compressor enters the refrigerant circuits at the top. This arrangement provides<br />

flexibility between the condensing <strong>and</strong> subcooling areas. As the condensate increases, part <strong>of</strong> the<br />

condensing area can be used as subcooling for the storage <strong>of</strong> liquid refrigerant. A receiver is necessary<br />

only when not all the liquid refrigerant can be stored in the condenser coil during the shutdown<br />

period <strong>of</strong> the refrigerant plant in winter. Cooling <strong>air</strong> is usually forced through the coil by a propeller<br />

fan, as shown in Fig. 10.11. A propeller fan has a lower fan total pressure <strong>and</strong> large volume flow<br />

rate, which make it more suitable for <strong>air</strong>-cooled condensers. Fans are usually located downstream<br />

from the coils in order to provide an even <strong>air</strong>stream through the coils. A damper may be installed<br />

after or before the fan to modulate the <strong>air</strong> volume flow rate. In a small <strong>air</strong>-cooled condenser, the<br />

coils, propeller fan, <strong>and</strong> damper may be installed in line horizontally. In large <strong>air</strong>-cooled condensers,<br />

condensing <strong>and</strong> subcooling coils are usually located on two sides, <strong>and</strong> the propeller fans<br />

<strong>and</strong> dampers are at the top <strong>of</strong> the unit.<br />

Heat-Transfer Processes <strong>and</strong> Temperature Curves<br />

Heat-transfer processes in a typical <strong>air</strong>-cooled condenser using HCFC-22 as refrigerant are divided<br />

into three stages, as shown in Fig. 10.11b: desuperheating <strong>of</strong> hot gas, condensation <strong>of</strong> liquid refrigerant,<br />

<strong>and</strong> subcooling. Desuperheating uses about 5 percent <strong>of</strong> the condensing surface area, condensation<br />

uses 85 to 90 percent, <strong>and</strong> subcooling uses 5 to 10 percent.<br />

For a condenser coil with a depth <strong>of</strong> two to three rows, <strong>air</strong>flow <strong>and</strong> refrigerant flow are usually in<br />

a combined counterflow <strong>and</strong> cross-flow arrangement. Air enters the condenser coil at a temperature<br />

equal to the summer outdoor design dry-bulb temperature T o. In a year <strong>of</strong> average weather, T o is the<br />

temperature whose annual cummulative frequency <strong>of</strong> occurrence is about 0.01 � 8760 � 88 h. If<br />

the <strong>air</strong>-cooled condenser is installed on the ro<strong>of</strong>, an additional 3 to 5°F (1.7 to 2.8°C) should be

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!