FIGURE 13.5 (Continued )<br />

REFRIGERATION SYSTEMS: CENTRIFUGAL 13.11<br />

Occupied Cooling Mode. Cooling mode operation takes place when the space temperature in the<br />

perimeter zone T r, p � 75°F (23.9°C). The occupied cooling mode starts when the chilled water<br />

pump P1 is turned on (see Fig. 13.5a). Meanwhile, hot water pump P2 remains inactive; tower<br />

pump P3 forces all the condenser water to flow through the tower bundle, modulation valve V3, <strong>and</strong><br />

back to the cooling tower. Chilled water is then supplied to the perimeter zone through zone pump<br />

FIGURE 13.6 Heat recovery system using an auxiliary condenser.