23.10 CHAPTER TWENTY-THREE<br />

Under base ventilation, the amount <strong>of</strong> exfiltration required to maintain a space positive pressure <strong>of</strong><br />

� 0.005 in. WG (1.25 Pa) can be calculated as<br />

The volume flow rate <strong>of</strong> base ventilation is then<br />

or roughly 1200 cfm (566 L/s), that is, 1200/20,000 � 0.06 cfm/ft 2 (0.30 L/s� m2 ) <strong>of</strong> floor area,<br />

which is about 43 percent <strong>of</strong> the value <strong>of</strong> the minimum outdoor <strong>air</strong> required (V˙<br />

bv � 0.43 V˙<br />

o,sys) .<br />

Formaldehyde <strong>and</strong> other possible indoor <strong>air</strong> contaminants in the space<br />

should be measured. If their concentrations are above allowable levels, or if the building shell is too<br />

leaky, the base ventilation should be increased accordingly.<br />

The amount <strong>of</strong> outdoor ventilation <strong>air</strong> provided for CO2-based dem<strong>and</strong>-controlled ventilation in<br />

a VAV system in an <strong>of</strong>fice building with a ceiling height <strong>of</strong> 9 ft (2.7 m) during various operating<br />

modes is as follows:<br />

cfm/ft2 (L/s�m2 ) <strong>of</strong> floor area ach<br />

Air economizer cycle, free-cooling mode 0.14–1.3 (0.7–6.5) 0.93–10<br />

Minimum outdoor <strong>air</strong> recirculating mode<br />

V · o,sys (at design occupancy)<br />

Base ventilation V<br />

0.14 (0.7) 0.93<br />

· bv (lower limit) 0.06 (0.25) 0.40<br />

The volume flow rate <strong>of</strong> minimum outdoor <strong>air</strong> during recirculating mode at design occupancy is the<br />

calculated system outdoor <strong>air</strong> intake in the AHU or PU at summer design conditions V˙ o,sys by Eq.<br />

(23.3).<br />

It is recommended that a purge operation take place every weekday morning if the concentration<br />

<strong>of</strong> the volatile organic compounds or other indoor contaminants is above the allowable level before<br />

the building is occupied or if the difference between the indoor <strong>and</strong> outdoor CO2 concentrations is<br />

greater than 200 or 300 ppm.<br />

A CO 2-Based Dem<strong>and</strong>-Controlled Ventilation System<br />

�V˙ inf � 4005A e,l √�p � 4005 � 2.08 √0.005 � 589 cfm (278 L / s)<br />

V˙ bv � 600 � 589 � 1189 cfm<br />

Figure 23.3 shows a CO 2-based dem<strong>and</strong>-controlled ventilation system in a VAV system. It consists<br />

<strong>of</strong> a CO 2 sensor, a DDC unit controller, a minimum outdoor damper, an economizer damper, a recirculating<br />

damper, an exhaust damper, <strong>and</strong> damper motors. The CO 2 sensor is located in the return<br />

duct that connects the return ceiling plenum <strong>and</strong> the return fan inlet. During minimum outdoor <strong>air</strong><br />

recirculating mode:<br />

● The supply fan <strong>and</strong> the minimum outdoor <strong>air</strong> damper <strong>of</strong> this VAV system must have the capacity<br />

to provide the required amount <strong>of</strong> outdoor <strong>air</strong> at a volume flow rate <strong>of</strong> V˙ o,sys, in cfm (L/s), calculated<br />

by Eq. (23.3).<br />

● Outdoor <strong>air</strong> should be supplied to the occupied zone with a high ventilation effectiveness for the<br />

dilution <strong>of</strong> the concentration <strong>of</strong> CO2 <strong>and</strong> other indoor contaminants.<br />

● During commissioning, damper settings <strong>of</strong> required minimum outdoor <strong>air</strong> at design occupancy<br />

V˙<br />

o,sys,<br />

<strong>and</strong> base ventilation V˙ bv should be clearly marked, <strong>and</strong> the relationship between the measured<br />

CO2 concentration <strong>and</strong> the minimum outdoor damper opening setting from V˙ bv up to V˙ o,sys<br />

should be determined after tests.<br />

● When a VAV system is in the occupied, minimum outdoor <strong>air</strong> recirculating mode, after supply<br />

<strong>and</strong> return fans start, the minimum outdoor damper should be opened to an opening setting <strong>of</strong><br />

base ventilation.