21.54 CHAPTER TWENTY-ONE<br />

Percentage <strong>of</strong> zone peak (design) supply flow<br />

80<br />

60<br />

40<br />

20<br />

0<br />

Heating<br />

Cooling<br />

Dead<br />

b<strong>and</strong><br />

FIGURE 21.16 Supply volume flow rate <strong>of</strong> a control zone in the perimeter zone served by a fan-powered VAV system.<br />

Fan Energy Use<br />

.<br />

Vsn, r<br />

.<br />

V sn, c<br />

T s�n<br />

. .<br />

�<br />

V sn, c<br />

In a fan-powered VAV system, there are two kinds <strong>of</strong> fan energy use: the supply fan energy use in<br />

an AHU or a PU <strong>and</strong> the energy use <strong>of</strong> the small centrifugal fans in the fan-powered boxes. Typical<br />

supply fan efficiency is about 60 percent, <strong>and</strong> the motor efficiency is around 90 percent, which<br />

gives a combined fan <strong>and</strong> motor efficiency <strong>of</strong> about 55 percent.<br />

According to Elleson (1993), the efficiency <strong>of</strong> fans in fan-powered boxes from four manufacturers<br />

ranged from 16 to 35 percent, <strong>and</strong> the motor efficiency ranged from 45 to 55 percent. Assuming<br />

a fan efficiency <strong>of</strong> 30 percent <strong>and</strong> a motor efficiency <strong>of</strong> 50 percent, the combined fan <strong>and</strong> motor efficiency<br />

for the fan in the fan-powered box is 15 percent.<br />

Elleson (1993) has collected detailed data for the 1988 cooling season from the fourth floor <strong>of</strong> a<br />

12-story building in southern California using a fan-powered VAV system (parallel fan-powered<br />

boxes). The results are as follows:<br />

55°F (12.8°C) Supply <strong>air</strong> 45°F (7.2°C) Supply <strong>air</strong><br />

Fan-powered Fan-powered<br />

Supply fan boxes Total Supply fan boxes Total<br />

Continuous operation, kWh 11,720 7,000 18,720 7,794 7,000 14,794<br />

Intermittent operation, kWh 11,720 1,861 13,581 7,794 2,140 9,934<br />

No fan-powered boxes, kWh 11,720 0 11,720 8,417 0 8,417<br />

Intermittent operation indicates that fans in parallel fan-powered boxes operated only when the cold<br />

primary <strong>air</strong>flow fell below 50 percent <strong>of</strong> design flow.<br />

V sn, r<br />

80<br />

60<br />

40<br />