16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

21.32 CHAPTER TWENTY-ONE<br />

For the winter heating mode operation in the perimeter zone <strong>of</strong> a VAV reheat system, the following<br />

is recommended:<br />

● If there is only one AHU or PU to serve both the perimeter <strong>and</strong> interior zones in a VAV reheat system<br />

<strong>and</strong> if the zone heating load linear density q h,ft � 120 Btu/h�ft (115 W/m), then the warm <strong>air</strong><br />

supply volume flow rate from the reheating box in heating mode operation (at cold primary <strong>air</strong><br />

minimum setting) should be proportionally increased to prevent excessive buoyancy effects.<br />

● It is more energy-efficient to use a perimeter heating VAV system; a dual-fan, dual-duct VAV<br />

system; or a fan-powered VAV system; or else the AHU or PU that serves the perimeter zone is<br />

separated from another AHU or PU serving the interior zone.<br />

Winter Cooling Mode Operation in Interior Zone<br />

At winter design conditions, the outdoor humidity ratio wo � 0.0017 lb/lb (kg/kg), <strong>and</strong> the space<br />

sensible cooling load in the interior zone may still equal that <strong>of</strong> summer design conditions. Therefore,<br />

the supply temperature differential for the interior zone is Tr � Ts � 20°F, or Ts � 72 �<br />

20 � 52°F (11.1°C). The supply volume flow rate for the interior zone is still V˙ si � 6173 cfm<br />

(2913 L/s).<br />

If the same AHU or PU is used for both perimeter <strong>and</strong> interior zones, a minimum supply volume<br />

flow rate <strong>of</strong> cold primary <strong>air</strong> that equals 0.3 <strong>of</strong> the peak supply volume flow rate (including the<br />

required outdoor ventilation) is supplied to the perimeter zone during winter heating mode <strong>and</strong> can<br />

be calculated as<br />

The difference in humidity ratio between supply <strong>and</strong> zone <strong>air</strong> is<br />

where w r, w s � humidity ratio <strong>of</strong> zone <strong>and</strong> supply <strong>air</strong>, lb/lb (kg/kg). The temperature rise from the<br />

return system heat gain at winter design conditions is then<br />

<strong>and</strong><br />

If the temperature rise from the supply fan power is still about 2°F (1.1°C) <strong>and</strong> the temperature rise<br />

from supply duct heat gain is 3°F (1.7°C) for the interior zone, then<br />

<strong>and</strong><br />

�<br />

V˙ sx,c<br />

V˙ sx,c � 0.3 � 13,054 � 3916 cfm (1848 L / s)<br />

�T ret,w �<br />

w r � w s �<br />

13,300 � 13,300<br />

60 � (6173 � 3916) � 0.075 � 1061<br />

3<br />

(6173 � 3916) / 19,227<br />

T ru � T r ��T ret,w � 72 � 5.7 � 2 � 79.7�F (26.5�C)<br />

T m � T s � (2 � 3) � 52 � (2 � 3) � 47°F (7.2°C)<br />

T ru � T m<br />

T ru � T o<br />

�<br />

� V˙ o<br />

V˙ s<br />

79.7 � 47<br />

79.7 � 20<br />

� 0.55<br />

� 0.00055 lb / lb (kg / kg)<br />

� 5.7�F (3.2�C)<br />

From the psychrometric chart, at a temperature T r � 72°F (22.2°C) <strong>and</strong> � r � 30 percent,<br />

w r � 0.005 lb/lb (kg/kg). Draw line r-s from point r with SHR s � 0.84, which intersects the<br />

Q rl<br />

60V˙ s� sh fg, o

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!