16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

23.4 CHAPTER TWENTY-THREE<br />

The new St<strong>and</strong>ard 62-1999 contains the entire 1989 version, unchanged, along with the following<br />

four new addenda:<br />

● Addenda 62e removes the statement that ventilation rates in Table 2 accommodate a moderate<br />

amount <strong>of</strong> smoking because <strong>of</strong> the dangerousness <strong>of</strong> second-h<strong>and</strong> tobacco smoke.<br />

● Addenda 62c removes the requirement that the temperature <strong>and</strong> humidity conditions specified in<br />

St<strong>and</strong>ard 55 be maintained in all ventilated space, such as even in garages.<br />

● Addenda 62d rewords the st<strong>and</strong>ard scope to state that compliance with the st<strong>and</strong>ard will not ensure<br />

acceptable indoor <strong>air</strong> quality.<br />

● Addenda 62f clarifies that carbon dioxide (CO 2) is simply a useful indicator <strong>of</strong> the concentration<br />

<strong>of</strong> human bioeffluents.<br />

For details, refer to ASHRAE St<strong>and</strong>ard 62-1999. St<strong>and</strong>ard 62-1999 is under continuous maintenance<br />

by a St<strong>and</strong>ing St<strong>and</strong>ard Project Committee for which the St<strong>and</strong>ards Committee has established<br />

a documented program for regular publication <strong>of</strong> addenda or revisions.<br />

Recirculation <strong>of</strong> Unused Outdoor Air in Multizone Systems<br />

For a multizone VAV system, the ratio <strong>of</strong> outdoor <strong>air</strong> to supply <strong>air</strong> required to meet the ventilation<br />

<strong>and</strong> thermal load requirements is <strong>of</strong>ten different from zone to zone. The system ventilation <strong>air</strong> required,<br />

in most cases, is actually the amount <strong>of</strong> outdoor <strong>air</strong> intake at the AHU or PU. The problem<br />

is how the system-fixed ratio <strong>of</strong> outdoor <strong>air</strong> to supply <strong>air</strong> can satisfy the different ratios <strong>of</strong> outdoor<br />

<strong>air</strong> to supply <strong>air</strong> in various control zones.<br />

In a specific control zone, if the ratio <strong>of</strong> outdoor <strong>air</strong> to supply <strong>air</strong> is higher than is needed in this<br />

zone, the result is an increase in unused outdoor <strong>air</strong> in the recirculating <strong>air</strong> (more truly, the concentration<br />

<strong>of</strong> <strong>air</strong> contaminants is lower) which raises the dilution power <strong>of</strong> the supply <strong>air</strong> (including<br />

outdoor <strong>and</strong> recirculating <strong>air</strong>) for other control zones.<br />

Methods <strong>of</strong> calculating ventilation requirements using the unused outdoor <strong>air</strong> contained in recirculating<br />

<strong>air</strong> were developed in Australia <strong>and</strong> are included in ASHRAE St<strong>and</strong>ard 62-1999. The required<br />

corrected fraction <strong>of</strong> outdoor <strong>air</strong> supply in system supply <strong>air</strong> Y, in cfm (L/s), considering the<br />

outdoor requirement <strong>of</strong> the critical zone <strong>and</strong> the unused outdoor <strong>air</strong> contained in the recirculating<br />

<strong>air</strong> can be calculated as<br />

<strong>and</strong><br />

Y �<br />

X<br />

1 � X � Z<br />

Y � V˙ o,cor / V˙ s<br />

X � V˙ o,sys / V˙ s<br />

Z � V˙ o,cr / V˙ s,cr<br />

where V˙<br />

s � supply volume flow rate <strong>of</strong> <strong>air</strong> system, cfm (L/s)<br />

V˙ o,cor � corrected outdoor <strong>air</strong> supply volume flow rate, considering critical zone <strong>and</strong> unused<br />

outdoor <strong>air</strong> in the recirculating <strong>air</strong>, cfm (L/s)<br />

V˙ o,sys � calculated system outdoor <strong>air</strong> volume flow rate, cfm (L/s)<br />

V˙ o,cr � outdoor <strong>air</strong> volume flow rate required in critical zone, cfm (L/s)<br />

V˙ s,cr � critical zone supply volume flow rate, cfm (L/s)<br />

X � uncorrected fraction <strong>of</strong> outdoor <strong>air</strong> supply<br />

Y � corrected fraction <strong>of</strong> outdoor <strong>air</strong> supply<br />

Z � fraction <strong>of</strong> outdoor <strong>air</strong> in supply <strong>air</strong> in critical zone<br />

(23.1)<br />

(23.2)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!