Air Economizer Cycle<br />

If the difference in <strong>air</strong> density is ignored, the volume flow balance between the incoming infiltrated<br />

<strong>air</strong> <strong>and</strong> outward exhaust <strong>air</strong> in this <strong>air</strong> system becomes<br />

The volume flow <strong>of</strong> incoming <strong>air</strong> <strong>and</strong> exhaust <strong>air</strong> entering <strong>and</strong> leaving the system is nearly balanced.<br />

From the above analysis, the system operating point at 50 percent design volume flow rate, point<br />

Q, has a supply volume flow <strong>of</strong> 10,000 cfm (4719 L/s) <strong>and</strong> a fan total pressure<br />

�p t50 � 0.75 � 0.84 � 0.13 � 1.72 in. WC (428 Pa)<br />

During minimum outdoor <strong>air</strong> recirculating mode at 50 percent design volume flow, the volume flow<br />

rate <strong>of</strong> outdoor <strong>air</strong> extracted through the outdoor intake passage decreases to 1870 cfm (883 L/s).<br />

Space is maintained at a negative pressure <strong>of</strong> � 0.03 in. WG (� 7.5 Pag). An infiltration rate <strong>of</strong> 347<br />

cfm (164 L/s) enters the space through openings <strong>and</strong> cracks in the building shell.<br />

The pt�V˙ characteristics at key points during 50 percent design volume flow are as follows:<br />

When an <strong>air</strong> economizer cycle is operated at a design flow rate <strong>of</strong> 100 percent <strong>of</strong> outdoor <strong>air</strong> in this<br />

<strong>air</strong> system with a single supply fan <strong>and</strong> an exhaust fan combination, the recirculating damper is<br />

closed, <strong>and</strong> both the minimum outdoor damper <strong>and</strong> the other, large outdoor damper for the <strong>air</strong> economizer<br />

cycle are fully opened. Outdoor <strong>air</strong> is extracted to the mixed plenum, through the filters <strong>and</strong><br />

coils, <strong>and</strong> is supplied to the conditioned space. Because only a small portion <strong>of</strong> supply <strong>air</strong> is exhausted<br />

<strong>and</strong> exfiltrated, the space positive pressure increases to about 0.2 in. WG (50 Pag). The<br />

barometric relief damper then opens. Most <strong>of</strong> the supply <strong>air</strong> is discharged through the relief damper<br />

outdoors.<br />

When the supply <strong>and</strong> exhaust fan combination is operated at 50 percent design volume flow in<br />

the <strong>air</strong> economizer cycle, space pressure is still limited to 0.2 in. WG (50 Pa), <strong>and</strong> most <strong>of</strong> the supply<br />

<strong>air</strong> is discharged through the relief damper outdoors, as in the design volume flow.<br />

Warm-Up <strong>and</strong> Cool-Down Mode<br />

During the warm-up <strong>and</strong> cool-down mode, the outdoor damper is closed <strong>and</strong> the recirculating<br />

damper is fully open, while the exhaust fan is turned <strong>of</strong>f. Recirculated <strong>air</strong> from the space is conditioned<br />

in the packaged unit <strong>and</strong> is then supplied to the space. Because <strong>of</strong> the negative pressure in<br />

the mixing box, outdoor <strong>air</strong> is leaked into the box through the closed outdoor dampers <strong>and</strong> is exfiltrated<br />

from the space because <strong>of</strong> the higher positive space pressure.<br />

Pressure Variation at the Mixing Box<br />

AIR SYSTEMS: FAN COMBINATION AND SMOKE CONTROL 22.13<br />

V˙ o � V˙ inf � V˙ ex � 1870 � 347 � (3000 � 810) ��27 cfm (13 L / s)<br />

Point o Point m Point r Point ru<br />

p, in. WG<br />

V<br />

0 � 0.162 � 0.03 � 0.065<br />

· , cfm 1870 10,000 10,000 8157<br />

During the recirculating mode, when the supply volume flow rate is reduced from design flow to 50<br />

percent <strong>of</strong> design flow, the decrease in the recirculating volume flow rate causes a corresponding<br />

drop in the pressure loss <strong>of</strong> the recirculation system. Therefore, the pressure at the mixed plenum,<br />

p m increases from � 0.52 to � 0.16 in. WG (� 129 to � 40 Pag). The greater the pressure loss <strong>of</strong><br />

the return system at the design flow rate, the higher the fluctuation <strong>of</strong> �p om. Because <strong>of</strong> the reduced<br />

volume flow rate at a higher fan total pressure <strong>of</strong> the exhaust fan at 50 percent design flow, in order