16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

28.2 CHAPTER TWENTY-EIGHT<br />

● Four-pipe fan-coil <strong>air</strong> <strong>conditioning</strong> systems, or simply four-pipe fan-coil systems<br />

● Two-pipe fan-coil <strong>air</strong> <strong>conditioning</strong> systems, or simply two-pipe fan-coil systems<br />

● Water-source heat pump systems<br />

Advantages <strong>and</strong> Disadvantages<br />

Space <strong>conditioning</strong> systems have the following advantages compared to central <strong>and</strong> packaged systems:<br />

● Both heating <strong>and</strong> cooling devices in the form <strong>of</strong> terminals, such as fan coils or water-source heat<br />

pumps, are installed directly above or within the conditioned space, or very near to it. There is no<br />

return duct in a space <strong>conditioning</strong> system except the large core water-source heat pumps. Only a<br />

delivery outlet or a short recirculating duct supplies conditioned <strong>air</strong> to the perimeter zone.<br />

● As discussed in Sec. 20.9, a separately dedicated outdoor ventilation system is always required to<br />

provide ventilation <strong>air</strong> for occupants as well as the necessary exhaust <strong>air</strong>. At the same time, a<br />

space recirculating system is used to condition the recirculating <strong>air</strong> for fan-coil <strong>and</strong> water-source<br />

heat pump systems. The required amount <strong>of</strong> ventilation is always guaranteed, <strong>and</strong> a dedicated outdoor<br />

<strong>air</strong> ventilation system facilitates the adoption <strong>of</strong> dem<strong>and</strong>-controlled ventilation. The <strong>air</strong> economizer<br />

cycle for free cooling is only limited to the volume flow <strong>of</strong> the outdoor ventilation <strong>air</strong>.<br />

In space <strong>conditioning</strong> systems except the large core water-source heat pumps, the outdoor ventilation<br />

<strong>air</strong> duct is probably the only main duct with comparatively less headroom required than in<br />

the supply duct that crosses under the beams in the ceiling plenum.<br />

● Both four-pipe fan coils <strong>and</strong> console water-source heat pumps provide individual zone control<br />

with each fan coil or each console water-source heat pump serving an individual zone. There is<br />

<strong>of</strong>ten an additional high-low speed or high-medium-low speed control on the volume flow <strong>of</strong> the<br />

supply fan. The four-pipe fan coil or the water-source heat pump can be changed from cooling<br />

mode to heating mode <strong>and</strong> vice versa automatically or manually, <strong>and</strong> it adjusts its capacity to<br />

meet the variation <strong>of</strong> the zone load during part-load operation.<br />

● There is less cross-contamination between rooms <strong>and</strong> control zones.<br />

● According to Zaidi <strong>and</strong> Howell (1993), the energy use <strong>of</strong> a four-pipe fan-coil system was only 73<br />

percent compared with a VAV reheat system, <strong>and</strong> the energy use <strong>of</strong> a water-source heat pump was<br />

only 63 percent that <strong>of</strong> a VAV system. Anantapantula <strong>and</strong> Sauer (1994) found that the energy use<br />

<strong>of</strong> a four-pipe fan-coil system compared to a VAV reheat system was even lower. Lower energy<br />

use in fan-coil <strong>and</strong> water-source heat pump systems is due to the following:<br />

First, there is far less energy required to transport the conditioned <strong>air</strong> <strong>and</strong> the recirculating <strong>air</strong>;<br />

also, no energy is needed to transport the return <strong>air</strong>.<br />

Second, a fan-coil system can transfer excess heat from the interior zone <strong>of</strong> a building to the<br />

perimeter zone through a heat recovery system, as discussed in Sec. 13.3. A water-source heat<br />

pump operated in heating mode can absorb the heat rejected by another water-source heat pump<br />

that is operated in cooling mode <strong>and</strong> recovers it for heating in the perimeter zone.<br />

Space <strong>conditioning</strong> systems have the following disadvantages:<br />

● Only low-efficiency filters are used in fan coils <strong>and</strong> water-source heat pumps. Low efficiency <strong>air</strong><br />

filters are unable to remove particulates <strong>of</strong> size � 3 �m <strong>and</strong> are ineffective at proving an acceptable<br />

IAQ for occupants as well as protecting the coils <strong>and</strong> components in the <strong>air</strong> distribution system<br />

from dust <strong>and</strong> contaminants.<br />

● Fan-coil systems reduce the chilled water flow rate to decrease their cooling capacity during part<br />

load. Therefore, this results in a significantly higher zone relative humidity at part-load operation.<br />

The zone relative humidity may increase to 70 percent at part load, especially when the fan coil is<br />

oversized.<br />

● Because fan coils <strong>and</strong> water source heat pumps are <strong>of</strong>ten mounted directly above or near to the<br />

conditioned space, they may create a noise problem, as discussed in Sec. 26.2, which is always

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!