16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Design Considerations<br />

AIR SYSTEMS: VARIABLE-AIR-VOLUME SYSTEMS 21.55<br />

If series fan-powered boxes <strong>and</strong> parallel fan-powered boxes are both operated continuously, the<br />

energy use <strong>of</strong> the supply fan plus the fans in the parallel fan-powered boxes consume less than onehalf<br />

<strong>of</strong> the kWh used by the supply fan plus the fans in the series fan-powered boxes in 45°F<br />

(7.2°C) cold <strong>air</strong> distribution.<br />

● Because there are two mixings (the mixing <strong>of</strong> outdoor <strong>air</strong> <strong>and</strong> recirculating <strong>air</strong> in the AHU or PU<br />

<strong>and</strong> the mixing <strong>of</strong> cold primary <strong>air</strong> <strong>and</strong> plenum <strong>air</strong> in the fan-powered box), adequate supply <strong>of</strong><br />

outdoor <strong>air</strong> is critical in a fan-powered VAV system. This is discussed in Chap. 23.<br />

● In a VAV system using cold <strong>air</strong> distribution, fan-powered boxes can be installed in both the<br />

perimeter <strong>and</strong> interior zones, or in the perimeter zone only, for lower initial cost. Cold primary <strong>air</strong><br />

is supplied directly to the interior zone by high-induction ceiling diffusers, as shown in<br />

Fig. 18.10a <strong>and</strong> b.<br />

● The mixing ratio <strong>of</strong> cold primary <strong>air</strong> to zone supply <strong>air</strong> <strong>and</strong> the reset <strong>of</strong> the cold primary <strong>air</strong> supply<br />

temperature for the perimeter zone are different from those <strong>of</strong> the interior zone. Different<br />

AHUs or PUs are preferable for the perimeter zone <strong>and</strong> interior zone separately. An analysis <strong>of</strong><br />

energy savings <strong>and</strong> investment costs is <strong>of</strong>ten necessary.<br />

● In a series fan-powered box, the supply fan in the AHU or PU <strong>of</strong>fsets the system pressure drop up<br />

to the inlet <strong>of</strong> the VAV box. The fan in the fan-powered box <strong>of</strong>fsets the pressure drop <strong>of</strong> the VAV<br />

box, elbows (if any), downstream heating coil, flexible duct, <strong>and</strong> diffuser.<br />

In a parallel fan-powered box, the supply fan in the AHU or PU <strong>of</strong>fsets the pressure drop <strong>of</strong><br />

the VAV box, flexible duct, diffuser, <strong>and</strong> straight-through mixing loss <strong>of</strong> the cold primary<br />

<strong>air</strong>stream in the fan-powered box.<br />

● At summer <strong>and</strong> winter design conditions, the ratio <strong>of</strong> the volume flow rate <strong>of</strong> cold primary <strong>air</strong><br />

supplied to the fan-powered box to the zone supply volume flow rate V˙ sn,c/V˙<br />

sn,d <strong>and</strong> the ratio <strong>of</strong><br />

the volume flow rate <strong>of</strong> warm recirculating plenum <strong>air</strong> to the zone supply volume flow rate<br />

V˙ s,rec/V˙<br />

sn,d depend on the following factors: (1) zone sensible cooling load <strong>and</strong> heating load,<br />

(2) zone supply temperature differential at summer <strong>and</strong> winter design conditions Trn � Tsn,d, or<br />

Tsn,d � Trn, <strong>and</strong> (3) outdoor <strong>air</strong> requirements.<br />

As mentioned previously, for cold <strong>air</strong> distribution V˙ sn,c /V˙ sn,d is about 0.6 for a fan-powered<br />

box. The winter heating in the perimeter zone <strong>of</strong>ten needs greater supply volume flow to match<br />

the requirement <strong>of</strong> the warm <strong>air</strong> supply temperature differential not exceeding 15°F (8.3°C);<br />

V˙<br />

sn,h /V˙ sn,d for cold <strong>air</strong> distribution is about 0.7.<br />

● The supply main ducts, branch ducts, cold <strong>air</strong> passage in the VAV box, flexible ducts, <strong>and</strong> diffusers<br />

must be well insulated especially for cold <strong>air</strong> distribution. Cold primary <strong>air</strong> <strong>and</strong> recirculated<br />

plenum <strong>air</strong> should be mixed in a perpendicular flow direction to prevent downstream temperature<br />

stratification.<br />

● A low zone relative humidity <strong>and</strong> zone dew point are desirable to prevent possible surface condensation<br />

during cold <strong>air</strong> distribution. When cold primary <strong>air</strong> at 44°F (6.7°C) is supplied directly<br />

to the conditioned space through high induction diffusers, the surface <strong>of</strong> the induction diffusers<br />

can be assumed to be 3°F (1.7°C) higher than the supply <strong>air</strong>; or the dew point <strong>of</strong> zone <strong>air</strong> should<br />

be lower than 44 � 3 � 47°F (8.3°C), that is, a zone temperature <strong>of</strong> 75°F (23.9°C) <strong>and</strong> a space<br />

relative humidity �r � 37 percent.<br />

● At the start <strong>of</strong> cool-down period in a hot <strong>and</strong> humid summer, direct supply <strong>of</strong> 40 to 50°F (4.4 to<br />

10.0°C) cold primary <strong>air</strong> to the fan-powered boxes may cause condensation because <strong>of</strong> the higher<br />

dew point <strong>of</strong> stagnant <strong>air</strong> in the ceiling plenum before the cool-down period. The AHU or PU should<br />

supply 55°F (12.8°C) <strong>air</strong> to the fan-powered boxes first, to reduce moisture <strong>and</strong> lower the dew point.<br />

● If humidification is required to maintain an acceptable zone relative humidity in winter, a humidifier<br />

can be installed in the AHU or PU.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!